EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
3. Function Setting
The function setting should be performed during the outdoor unit stoppage.
This setting is not available during External Input/Output Setting.
No.
7-Segment Display
Setting Item
Contents
1
0
Circulator Function
at Heating Thermo-OFF
No setting (continuously operation)
1
Indoor fan forced ON and OFF (2min. ON/6min. OFF)
2
0
Night Shift (Low Noise)
No setting
1
Setting night shift for cooling
3
0
Cancellation of Outdoor
Ambient Temperature Limit
No setting (valid)
1
Cancellation for heating
2
Cancellation for cooling
3
Cancellation for cooling and heating
4
0
Change of Defrost
Condition
No setting
1
Defrost for cold area
2
Defrost for warm area
5
0
SLo (IU Fan Speed)
Defrost Setting
No setting (Indoor fan stoppage during defrost operation)
1
Indoor fan SLo operation when heating operation is activated/during defrost
operation
6
0
Cancellation of Hot Start
No setting
1
Cancellation of hot start
7
0
Priority Capacity Mode
No setting
1
Change of correction factor for compressor frequency (pattern1)
2
Change of correction factor for compressor frequency (pattern2)
3
Change of correction factor for compressor frequency (pattern3)
8
0
Compressor Frequency
Control Target Value for
Cooling
No setting
1
Change of upper limit for compressor frequency of cooling operation
9
0
Compressor Frequency
Control Target Value for
Heating
No setting
1
Change of upper limit for compressor frequency of heating operation
10
0
Compressor Frequency
Fixed Mode
No setting
1
Fixed frequency mode
Start
DSW1-No.4 is “ON”.
DSW2-No.5 is “ON”.
The menu indication is changed
by pressing PSW2 or PSW3 and
PSW1 as shown by arrows (below).
End
DSW2-No.5 is “OFF”.
DSW1-No.4 is “OFF”.
NOTES:
1. Record the function No. of each setting
when setting the optional function. The
example is for setting 1.
2. Record the setting No. on the nameplate
“External Input/ Output and Function Setting”
attached to the reverse surface of the service
cover as well.
Summary of Contents for Set Free mini-HNRQ1 Series
Page 8: ...1 Installation ...
Page 50: ...43 Troubleshooting ...
Page 60: ...53 d Noise Filter Board NF1 TROUBLESHOOTING ...
Page 123: ...121 Maintenance ...
Page 153: ...External Input Output and Function Setting 151 ...
Page 167: ...Field Work Instructions 165 ...
Page 172: ...Service Parts List 170 ...
Page 175: ...173 SERVICE PARTS LIST RAS 3 0HNBRKQ1 RAS 3 5HNBRKQ1 ...
Page 176: ...174 SERVICE PARTS LIST RAS 3 0HNBRKQ1 RAS 3 5HNBRKQ1 ...
Page 177: ...175 SERVICE PARTS LIST RAS 4 0HNBRKQ1 RAS 4 5HNBRKQ1 RAS 5 0HNBRKQ1 ...
Page 178: ...176 SERVICE PARTS LIST RAS 4 0HNBRKQ1 RAS 4 5HNBRKQ1 RAS 5 0HNBRKQ1 ...
Page 179: ...177 SERVICE PARTS LIST RAS 6 0HNBRKQ1 RAS 6 5HNBRKQ1 ...
Page 180: ...178 SERVICE PARTS LIST RAS 6 0HNBRKQ1 RAS 6 5HNBRKQ1 ...
Page 183: ...181 SERVICE PARTS LIST RAS 7 0HNBRMQ1 RAS 8 0HNBRMQ1 ...
Page 184: ...182 SERVICE PARTS LIST RAS 7 0HNBRMQ1 RAS 8 0HNBRMQ1 ...
Page 185: ...183 SERVICE PARTS LIST RAS 10HNBRMQ1 RAS 11HNBRMQ1 RAS 12HNBRMQ1 ...
Page 186: ...184 SERVICE PARTS LIST RAS 10HNBRMQ1 RAS 11HNBRMQ1 RAS 12HNBRMQ1 ...
Page 187: ...HS2019266A ...