63
Fan 1 Motor Current
22
0~9.9(A)
Fan 2 Motor Current
23
0~9.9(A)
Indoor Unit Address
24
0~63
(Indoor Unit No.)
Indoor Electronic Expansion Valve Opening
25
0
~
100(%)
Liquid Pipe Temp. of Indoor Unit
26
*1
-19
~
127(°C)
Gas Pipe Temp. of Indoor Unit
27
*1
-19
~
127(°C)
Indoor Unit Inlet Air Temp.
28
*1
-19
~
127(°C)
Indoor Unit Outlet Air Temp.
29
*1
-19
~
127(°C)
Cause Code of Indoor Unit Stoppage
30
0~99
Accumulated Operating Time of Comp.
150
*2*3 0000
~
9999(×10 hours)
Accumulated Operating Time of Compressor
(Restorable)
151
*2*3 0000
~
9999(×10 hours)
Outdoor Unit Alarm Code
152
00
~
FF
Cause Code of Comp. Inverter Stoppage
153
0
~
99
Cause Code of Fan Stoppage (Lower Outdoor Fan)
154
0
~
99
Cause Code of Fan Stoppage (Upper Outdoor Fan)
155
0
~
99
Abnormal Data Record (No.1)
156
……..
Accumulated Operating Time,
Alarm Code or Cause Code of I.U.
Stoppage, Cause Code of Inverter/
Fan Stoppage
……..
…
…
Abnormal Data Record (No.9)
Capacity of Outdoor unit
157
Capacity Code of Outdoor Unit. For
example, 40 represent that 40÷8=
[5]HP. Besides the 3HP, its capacity
code is 22.
Total Capacity of Indoor Unit Connected
158
*1
0
~
199
Connected Indoor Unit Number
159
0.
~
64. (pcs)
System Refrigerant Address
160
0
~
63 (Refrigerant System No.)
Notes
:
●
*1: When information number is over than 100, the last two digits flash.
For example
:
When number is "-19", SEG1 displays
When number is "120", SEG1 flashe
s
●
*2: Alternately upper 2 digits and lower 2 digits are indicated every 0.5 sec.
For example
:
When number is "194", SEG1 displays
alternately every 0.5 sec.
When number is "0", SEG1 displays
alternately every 0.5 sec.
When number is "-15", SEG1 displays
alternately every 0.5 sec.
●
*3: For resetting the Accumulated Operating Time (Restorable), press PSW1 for 5sec. While the Accumulated Operating Time
(Restorable) is indicated.
TROUBLESHOOTING
Summary of Contents for Set Free mini-HNRQ1 Series
Page 8: ...1 Installation ...
Page 50: ...43 Troubleshooting ...
Page 60: ...53 d Noise Filter Board NF1 TROUBLESHOOTING ...
Page 123: ...121 Maintenance ...
Page 153: ...External Input Output and Function Setting 151 ...
Page 167: ...Field Work Instructions 165 ...
Page 172: ...Service Parts List 170 ...
Page 175: ...173 SERVICE PARTS LIST RAS 3 0HNBRKQ1 RAS 3 5HNBRKQ1 ...
Page 176: ...174 SERVICE PARTS LIST RAS 3 0HNBRKQ1 RAS 3 5HNBRKQ1 ...
Page 177: ...175 SERVICE PARTS LIST RAS 4 0HNBRKQ1 RAS 4 5HNBRKQ1 RAS 5 0HNBRKQ1 ...
Page 178: ...176 SERVICE PARTS LIST RAS 4 0HNBRKQ1 RAS 4 5HNBRKQ1 RAS 5 0HNBRKQ1 ...
Page 179: ...177 SERVICE PARTS LIST RAS 6 0HNBRKQ1 RAS 6 5HNBRKQ1 ...
Page 180: ...178 SERVICE PARTS LIST RAS 6 0HNBRKQ1 RAS 6 5HNBRKQ1 ...
Page 183: ...181 SERVICE PARTS LIST RAS 7 0HNBRMQ1 RAS 8 0HNBRMQ1 ...
Page 184: ...182 SERVICE PARTS LIST RAS 7 0HNBRMQ1 RAS 8 0HNBRMQ1 ...
Page 185: ...183 SERVICE PARTS LIST RAS 10HNBRMQ1 RAS 11HNBRMQ1 RAS 12HNBRMQ1 ...
Page 186: ...184 SERVICE PARTS LIST RAS 10HNBRMQ1 RAS 11HNBRMQ1 RAS 12HNBRMQ1 ...
Page 187: ...HS2019266A ...