65
20
Sensor on
Outdoor Unit
Abnormality of Discharge Gas
Thermistor
Incorrect Wiring, Disconnected Wiring, Broken Wire Short Circuit
21
Abnormality of High Pressure Sensor
22
Abnormality of Outdoor Air Thermistor
24
Abnormality of Heat Exchanger
Piping Thermistor
29
Abnormality of Low Pressure Sensor
31
Incorrect Capacity Setting of Outdoor
Unit and Indoor Unit
Incorrect Capacity Code Setting of Combination Excessive or
Insufficient Indoor Unit Total Capacity Code
35
Incorrect Setting of Indoor Unit No.
Duplication of Indoor Unit No. in same Refrigerant Group
36
Incorrect of Indoor Unit Combination
Outdoor unit and indoor unit are different Tier, brand exception
combination
38
Problem with Protective Pick-up
Circuit in Outdoor Unit
Failure of Protection Detecting Device
(Incorrect Wiring of Outdoor PCB)
3E
Combination Problem between
Inverter PCB and Outdoor PCB
Incorrect Combination between Inverter PCB and Outdoor PCB
43
Sensor on
Outdoor Unit
Activation of Pressure
Ratio Decrease Protection
Defective Compression (Failure of Compressor or Inverter, Loose
Power Supply Connection)
44
Activation of Low Pressure Increase
Protection
Overload at Cooling, High Temperature at Heating, Expansion
Valve Locking at Open Position (Loose Connector)
45
Activation of High Pressure Increase
Protection
Overload Operation (Heat Exchanger Clogging, Short Circuit of
Airflow), Pipe Clogging, Excessive Refrigerant, Inert Gas Mixing
47
Activation of Low Pressure Decrease
Protection
Insufficient Refrigerant, Piping Clogging, Expansion Valve Locking
at Close Position (Loosen Connector)
48
Activation of Inverter Overcurrent
Overload Operation, Compressor Failure
51
Inverter
Abnormality of Current Sensor for
Inverter
Current Sensor Failure
53
Inverter Error Signal Detection
Driver IC Error Signal Detection (Protection for Overcurrent, Low
Voltage, Short Circuit)
54
Abnormality of Inverter Fin
Temperature
Abnormal Inverter Fin Thermistor, Heat Exchanger Clogging, Fan
Motor Failure
55
Inverter Failure
Inverter PCB Failure
57
Fan Controller
Abnormality of Fan Motor
Fan Motor Failure (Fan Motor Locking, Increase Fan Motor
Temperature, Blown Fuse)
5A
Abnormality ofFan Controller
FinTemperature
Fin Thermistor Failure, Heat Exchanger Clogging, Fan Motor
Failure
5b
Activation of Overcurrent Protection
Fan Motor Failure
5C
Problem with Fan Controller Sensor
Failure of Current Sensor
b0
Outdoor Unit No.
Setting
Incorrect Setting of Indoor Models
and Capacity
b1
Incorrect Setting of Unit and
Refrigerant System Number
There are 64 or More Numbers Set for Refrigerant
System.
TROUBLESHOOTING
Summary of Contents for Set Free mini-HNRQ1 Series
Page 8: ...1 Installation ...
Page 50: ...43 Troubleshooting ...
Page 60: ...53 d Noise Filter Board NF1 TROUBLESHOOTING ...
Page 123: ...121 Maintenance ...
Page 153: ...External Input Output and Function Setting 151 ...
Page 167: ...Field Work Instructions 165 ...
Page 172: ...Service Parts List 170 ...
Page 175: ...173 SERVICE PARTS LIST RAS 3 0HNBRKQ1 RAS 3 5HNBRKQ1 ...
Page 176: ...174 SERVICE PARTS LIST RAS 3 0HNBRKQ1 RAS 3 5HNBRKQ1 ...
Page 177: ...175 SERVICE PARTS LIST RAS 4 0HNBRKQ1 RAS 4 5HNBRKQ1 RAS 5 0HNBRKQ1 ...
Page 178: ...176 SERVICE PARTS LIST RAS 4 0HNBRKQ1 RAS 4 5HNBRKQ1 RAS 5 0HNBRKQ1 ...
Page 179: ...177 SERVICE PARTS LIST RAS 6 0HNBRKQ1 RAS 6 5HNBRKQ1 ...
Page 180: ...178 SERVICE PARTS LIST RAS 6 0HNBRKQ1 RAS 6 5HNBRKQ1 ...
Page 183: ...181 SERVICE PARTS LIST RAS 7 0HNBRMQ1 RAS 8 0HNBRMQ1 ...
Page 184: ...182 SERVICE PARTS LIST RAS 7 0HNBRMQ1 RAS 8 0HNBRMQ1 ...
Page 185: ...183 SERVICE PARTS LIST RAS 10HNBRMQ1 RAS 11HNBRMQ1 RAS 12HNBRMQ1 ...
Page 186: ...184 SERVICE PARTS LIST RAS 10HNBRMQ1 RAS 11HNBRMQ1 RAS 12HNBRMQ1 ...
Page 187: ...HS2019266A ...