PMML0251A rev.2 - 02/2013
Electrical wiring
39
ENGLISH
15.3.4 System installation DIP Switch Setting
Dip Switch Setting of Indoor PCB and Outdoor PCB for H-LINK II
It is required to set dip switches of every indoor unit and outdoor unit and match of the transmission circuit impedance.
• Dip Switch Setting Example:
Cycle nº 0
DSW5
Terminating Resistance
DSW4
Refrigerant Cycle Nº
(Setting for ten digit)
RSW1
Refrigerant Cycle Nº
(Setting for last digit)
Outdoor units
Indoor units
DSW5
Refrigerant Cycle Nº
(Setting for ten digit)
RSW2
Refrigerant Cycle Nº
(Setting for last digit)
DSW6
Indoor unit Address
(Setting for ten digit)
RSW1
Indoor unit Address
(Setting for last digit)
Cycle nº 1
Cycle nº 2
Unit
Name of Dip Switch
Mark
Setting Before
Shipment
Function
Outdoor Unit
Refrigerant Cycle
DSW4
RSW1
DSW4
RSW1
For setting refrigerant cycle address of Outdoor Unit. Set the DSW4
and RSW1 not to overlap the setting of other Outdoor units in the same
H-LINK system
Terminating Resistance DSW5
For matching impedance of transmission circuit, set the DSW5 accord-
ing to the quantity of outdoor units in the H-LINK system.
Indoor Unit
Refrigerant Cycle
DSW5
RSW2
DSW5
RSW2
For setting refrigerant cycle address of indoor units. Set the DSW5 and
RSW2 corresponding to the address of outdoor unit in the same refriger-
ant cycle.
Indoor Unit Address
DSW6
RSW1
DSW6
RSW1
For setting indoor unit address. Set the DSW6 and RSW1 not to overlap
the setting of other indoor units in the same refrigerant cycle. (If not set,
the automatic address function is performed).
_PMML0251A_r2.indb 39
06/02/2013 9:05:14
Summary of Contents for RAS-10HNCE
Page 2: ..._PMML0251A_r2 indb 2 06 02 2013 9 04 41 ...
Page 154: ...154 Dépannage PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 154 06 02 2013 9 06 33 ...
Page 226: ...226 PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 226 06 02 2013 9 07 28 ...
Page 298: ...298 Problemen oplossen PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 298 06 02 2013 9 08 18 ...
Page 371: ..._PMML0251A_r2 indb 371 06 02 2013 9 09 06 ...
Page 372: ...PMML0251A rev 2 02 2013 Printed in Spain _PMML0251A_r2 indb 372 06 02 2013 9 09 07 ...