Units installation
Blocked in Inlet Side
Upper Side Blocked
Single Installation
Multiple Installation (Two units or more)
100 mm or more of the side space is acceptable on the service cover
side.
Allow 100 mm of space between units. Leave open both right and left
sides..
Leave open both right and left sides.
Be sure to use the fan direction guide. Allow 100 mm of space between
units. Leave open both right and left sides.
No more than 2 units for multiple installation.
The length A is as shown in the following table:
L
A
0 < L ≤ 1/2H
600 or greater
1/2H < L≤ H
1400 or greater
When L > H use a base for outdoor unit to make L ≤ H.
Close the base not to allow the outlet air bypassed.
Outlet Side Blocked
Upper Side Open
Single Installation
Multiple Installation (Two units or more)
Allow 100 mm of space between units. Both right and left sides shall be
open.
Be sure to use the fan direction guide. Leave open both right and left
sides.
Be sure to use the fan direction guide. Allow 100 mm of space between
units. Leave open both right and left sides.
No more than 2 units for multiple installation.
The length A is as shown in the following table:
L
A
0 < L ≤ 1/2H
600 or greater
1/2H < L≤ H
1400 or greater
When L > H use a base for outdoor unit to make L ≤ H.
Close the base not to allow the outlet air bypassed.
_PMML0251A_r2.indb 20
06/02/2013 9:04:58
Summary of Contents for RAS-10HNCE
Page 2: ..._PMML0251A_r2 indb 2 06 02 2013 9 04 41 ...
Page 154: ...154 Dépannage PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 154 06 02 2013 9 06 33 ...
Page 226: ...226 PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 226 06 02 2013 9 07 28 ...
Page 298: ...298 Problemen oplossen PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 298 06 02 2013 9 08 18 ...
Page 371: ..._PMML0251A_r2 indb 371 06 02 2013 9 09 06 ...
Page 372: ...PMML0251A rev 2 02 2013 Printed in Spain _PMML0251A_r2 indb 372 06 02 2013 9 09 07 ...