PMML0251A rev.2 - 02/2013
Electrical wiring
37
ENGLISH
C A U T I O N
All the field wiring and electrical components must comply with
local codes.
15.3.1 Electrical wiring between indoor unit and
outdoor unit
• Connect the electrical wires between the indoor unit and the
outdoor unit, as shown below.
• Follow local codes and regulations when performing electrical
wiring.
• If the refrigerant piping and the control wiring are connected to
the units in the same refrigerant cycle.
• Use twist pair wire (more than 0.75 mm²) for operation wiring
between outdoor unit and indoor unit, and operation wiring
between indoor unit and indoor unit.
• Use 2-core wire for the operating line (Do not use wire with
more than 3 cores).
• Use shielded wires for intermediate wiring to protect the units
from noise obstacle at length of less than 300 m and size com-
plied with local code.
• Open a hole near the connection hole of power source wiring
when multiple outdoor units are connected from one power
source line.
• The recommended breaker sizes are detailed in the Wire size
section.
• In the case that a conduit tube for field-wiring is not used, fix
rubber bushes with adhesive on the panel.
• All the field wiring and equipment must comply with local and
international codes.
• H-LINK twist pair shielded cable must be grounded in the out-
door unit side.
C A U T I O N
Pay attention to the connection of the operating line. Incorrect
connection may cause the failure of PCB.
Power source from the outdoor unit to the indoor unit
Independent power source of outdoor unit and indoor unit
3
3
3
L1 L2 L3 N
L1 L2 L3 N
L1 L2 L3 N
No. 0 System
Outdoor unit
No. 0 System
Outdoor unit
Operating Line
(Shielded Pair Cable)
DC5V (Non-Pole Transmission,
H-LINK System)
Remote Control Switch
(Twisted Shielded Pair
Cable)
Operating Line
(Twisted Shielded
Pair Cable)
DC5V (Non-Pole
Transmission, H-LINK
System)
Indoor Unit
Indoor Unit
Terminal board
Circuit Breaker
Earthleakage Breaker
Field Wiring
Field supplied
Optional Accessory
Remote Control Switch
(Twisted Shielded Pair
Cable)
Indoor Unit
Indoor Unit
15.3 COMMON WIRING
Wiring example
Basic combinations (in the case of twin combination)
1
2
ON
DSW6
1
2
ON
DSW6
1
2
ON
DSW6
Operating line
Operating line
Operating line
Remote control
line
Remote control
line
Remote control
line
Individual control
Running ON/OFF individually
Thermo.ON/OFF individually
Individual control
Running ON/OFF simultaneously
Thermo.ON/OFF individually
Simultaneous control
Running ON/OFF simultaneously
Thermo.ON/OFF simultaneously
_PMML0251A_r2.indb 37
06/02/2013 9:05:13
Summary of Contents for RAS-10HNCE
Page 2: ..._PMML0251A_r2 indb 2 06 02 2013 9 04 41 ...
Page 154: ...154 Dépannage PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 154 06 02 2013 9 06 33 ...
Page 226: ...226 PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 226 06 02 2013 9 07 28 ...
Page 298: ...298 Problemen oplossen PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 298 06 02 2013 9 08 18 ...
Page 371: ..._PMML0251A_r2 indb 371 06 02 2013 9 09 06 ...
Page 372: ...PMML0251A rev 2 02 2013 Printed in Spain _PMML0251A_r2 indb 372 06 02 2013 9 09 07 ...