5 SETUP AND OPERATIONS
5-3
5.2 Set CPU Link Module Switches
(1) MAIN/SUB selector switch
Two CPU link modules can be mounted on a single CPU, each being connected to a separate
line.
Table 5-2 MAIN/SUB Selector Switch Settings
Number of units mounted
First
Second
One “0”
(main)
−
Two
“0” (main)
“1” (sub)
NOTE
Do not set the MAIN/SUB selector switch to 2 to F. Switch setting to 2 to 4 may
render the module inoperable or destroy transfer data (G000 to FFF).
(2) CPU No. selector switch
Set this selector switch to a number between 0 to F for each CPU that is connected to the CPU
link line. The CPU number that is set here differs from the PCs number that is set with a
special tool.
Ensure that the CPU link modules connected to the same line do not have their CPU numbers
set in duplicate.
CAUTION
Turn off the power before operating any switches. Operating switches with the
power turned on may cause the module to fail.