• Controller chassis: 4
• Drive chassis:
○
SFF: 16
○
LFF: 16
○
FMD: 8
Required number of PDUs per rack:
• Controller rack
○
Single phase: 4
○
Three phase: 2
• Drive rack:
○
Single phase: 4
○
Three phase: 2
Environmental specifications
The table lists the environmental specifications and requirements for the
storage system.
Table 18 VSP G1000, VSP G1500, and VSP F1500 environmental
specifications
Item
Operating
1
Not Operating
2
Shipping & Storage
3
Standard Temperature
(ºF / ºC)
61 to 90 / 16 to 32
-18 to 122
-10 to 35
-45 to 110 / -25 to 60
high temperature mode
(ºF / ºC)
60.8 to 104 / 16 to 40
Relative Humidity (%)
4
20 to 80
8 to 90
5 to 95
Max. Wet Bulb (ºF / ºC)
78.8 / 26
80.6 / 27
84.2 / 29
Temperature deviation
per hour (ºF / ºC)
50 / 10
50 / 10
68 / 20
Vibration
6
5 to 10Hz: 0.25 mm10 to
300Hz: 0.49m/s2
5 to 10Hz: 2.5mm10 to
70Hz: 4.9m/s270 to 99Hz:
0.05mm99 to 300Hz:
9.8m/s2
Sine Vibration: 4.9m/s2,
5min.At the resonant
frequency with the highest
displacement found
between 3 to 100Hz
7
Random Vibration:
0.147m2/s3, 30min, 5 to
100Hz
7
Shock
No impact
78.4m/s
2
(8.0G) 15ms
Horizontal: Incline Impact
1.22m/s
8
Vertical: Rotational Edge
0.15m
10
Dust
Less than 0.15mg per cubic
meter of air
-
-
Altitude
-60 m to 3,000 m
-
Site preparation
83