3. General data
TCGB0075 rev.0 - 11/2012
58
3.2.2 RAS-(4-6)HRNME-AF
Model
RAS-4HRNME-AF
RAS-5HRNME-AF
RAS-6HRNME-AF
Electrical power supply
3N~ 400V 50Hz
Color (Munsell code)
-
Natural gray (1.0Y8.5/0.5)
Sound pressure level
dB(A)
46
48
50
Sound power level
dB(A)
65
67
69
Outside measu-
rements
Height
mm
1,380
1,380
1,380
Width
mm
950
950
950
Depth
mm
370
370
370
Net weight
kg
107
108
108
Refrigerant
-
R-410A
Flow control
-
Microprocessor-controlled expansion valve
Compressor
-
DC inverter driven
Quantity
-
1
1
1
Power
kW
2.20
3.00
3.00
Heat exchanger
-
Multi-pass cross-finned tube
Condenser fan
-
Propeller fan
Quantity
-
1+1
1+1
1+1
Air flow rate
m³/min
80
90
100
Power
W
70+70
70+70
70+70
Refrigerant pipe connection
-
Flare-nut connection (factory supplied)
Size
Liquid piping
mm
(in)
Ø9.53
(3/8”)
Ø9.53
(3/8”)
Ø9.53
(3/8”)
Gas piping
mm
(in)
Ø15.88
(5/8”)
Ø15.88
(5/8”)
Ø15.88
(5/8”)
Refrigerant charge
kg
3.90
4.00
4.00
Maximum current
A
7.0
11.0
13.0
Packaging measurements
m³
0.70
0.70
0.70
N O T E
The sound pressure level is based on following conditions:
• 1 meter from the frontal surface of the unit; 1.5 meters from floor level.
•
Voltage of the power source is 400V.
The above data is measured in an anechoic chamber, so reflected sound should be taken into consideration
when installing the unit.