10. Electrical wiring
TCGB0075 rev.0 - 11/2012
118
10.3 Printed circuit board (PCB)
10.3.1 Outdoor unit
RAS-(4-6)H(V)RNME-AF
Connector indication
PCN1
Fuse
PCN2
PCB1 connection from outdoor to indoor unit
PCN5
Crankcase heater of compressor (oil)
PCN6
Output optional function
PCN7
Output optional function
PCN8
Pressure switch protection
PCN9
Compressor contactor
PCN13
Pressure switch control
THM7
Outdoor air temperature thermistor
THM8
Pipe evaporation temperature thermistor
THM9
Compressor discharge temperature thermistor
CN2
Current transformer
CN5A
Micro electronic expansion valve
CN8
Transmission from outdoor to indoor unit
CN14
Transmission between PCB1 and ISPM
EFS1, 2
Power protection
Switch indication
DSW1
(PCB1)
Test run
DSW2
Piping length and selection function
DSW3
Capacity code
DSW4/
RSW1
Refrigerant cycle number
DSW5
End terminal resistor
DSW6
Power source setting
LED indication
LED1
Red
This LED indicates the transmission status bet-
ween the indoor unit and the RCS
LED2
Yellow
This LED indicates the transmission status bet-
ween the indoor unit and the outdoor unit
LED3
Green
Power source for the PCB