3. General data
TCGB0075 rev.0 - 11/2012
56
3.1 YUTAKI S80 system
Model
Indoor unit
RWH-4.0FS(V)NFE
RWH-5.0FS(V)NFE
RWH-6.0FS(V)NFE
Outdoor unit
RAS-4H(V)RNME-AF
RAS-5H(V)RNME-AF RAS-6H(V)RNME-AF
Heating capacit
y
Nominal conditions
(Nominal)
Conditions: Water inlet/outlet: 30/35ºC
Outdoor temperature: (DB/WB): 7/6 ºC
kW
10.0
12.0
14.0
COP
-
4.36
4.27
4.05
(Nominal)
Conditions: Water inlet/outlet: 40/45ºC
Outdoor temperature: (DB/WB): 7/6 ºC
kW
10.0
12.0
14.0
COP
-
3.45
3.42
3.32
(Nominal)
Conditions: Water inlet/outlet: 47/55ºC
Outdoor temperature: (DB/WB): 7/6 ºC
kW
10.0
12.0
14.0
COP
-
3.04
3.02
3.01
(Nominal)
Conditions: Water inlet/outlet: 55/65ºC
Outdoor temperature: (DB/WB): 7/6 ºC
kW
10.0
12.0
14.0
COP
-
2.56
2.56
2.51
Additional conditions
(Nominal)
Conditions: Water inlet/outlet: (*)/35ºC
Outdoor temperature: (DB/WB): -7/-8 ºC
kW
7.6
9.0
9.4
COP
-
2.36
2.32
2.29
(Nominal)
Conditions: Water inlet/outlet: (*)/45ºC
Outdoor temperature: (DB/WB): -7/-8 ºC
kW
10.0
12.0
14.0
COP
-
2.30
2.30
2.25
(Nominal)
Conditions: Water inlet/outlet: (*)/55ºC
Outdoor temperature: (DB/WB): -7/-8 ºC
kW
10.0
12.0
14.0
COP
-
2.15
2.15
2.10
(Nominal)
Conditions: Water inlet/outlet: (*)/65ºC
Outdoor temperature: (DB/WB): -7/-8 ºC
kW
10.0
12.0
14.0
COP
-
2.00
1.91
1.81
N O T E
•
The nominal heating capacity is based on the EN 14511 standard: Piping length: 7.5 meters; Piping lift: 0 me-
ters.
• (*) Water inlet temperature is not fixed for additional conditions. The test is performed fixing the flow rate ob
-
tained during the test at nominal conditions:
-
Outdoor temperature: (DB/WB): 7/6 ºC
•
DB: dry bulb; WB: wet bulb.