10. Electrical wiring
TCGB0075 rev.0 - 11/2012
126
¡
DSW5: Additional setting 2
In the cases where the outdoor unit is installed into a location where its own outdoor ambient temperature sensor can not
give a suitable temperature measurement to the system, it is available the 2nd outdoor ambient temperature sensor as
accessory.
By means of DSW setting, it can be selected the preferable sensor for each circuit.
N O T E
Switch ON the DSW4-2 to enable this additional setting.
Factory setting
Outdoor unit sensor for circuits 1 and 2.
Outdoor unit sensor for circuit 1; Auxiliary
sensor for circuit 2.
Auxiliary sensor for circuit 1; Outdoor unit
sensor for circuit 2.
Auxiliary sensor instead of outdoor unit
sensor for both circuits.
Universal sensor enabled
Use Two3 (boiler / heater thermistor) ins-
tead Two (water outlet thermistor) for water
control
¡
DSW6: Not used
Factory setting
(Not change)
¡
DSW7: Not used
Factory setting
(Not change)
¡
DSW8: Not used
¡
DSW9: Not used
¡
RSW1 & RSW2: Refrigerant system setting
RSW1: Ten digits
RSW2: Unit digits
¡
RSW3 & RSW4: Indoor unit address setting
RSW3: Ten digits
RSW4: Unit digits