3. General data
TCGB0075 rev.0 - 11/2012
57
3
3.2 Outdoor unit
3.2.1 RAS-(4-6)HVRNME-AF
Model
RAS-4HVRNME-AF
RAS-5HVRNME-AF
RAS-6HVRNME-AF
Electrical power supply
1~ 230V 50Hz
Color (Munsell code)
-
Natural gray (1.0Y8.5/0.5)
Sound pressure level
dB(A)
46
48
50
Sound power level
dB(A)
65
67
69
Outside mea-
surements
Height
mm
1,380
1,380
1,380
Width
mm
950
950
950
Depth
mm
370
370
370
Net weight
kg
103
104
104
Refrigerant
-
R-410A
Flow control
-
Microprocessor-controlled expansion valve
Compressor
-
DC inverter driven
Quantity
-
1
1
1
Power
kW
1.80
2.50
2.50
Heat exchanger
-
Multi-pass cross-finned tube
Outdoor fan
-
Propeller fan
Quantity
-
2
2
2
Air flow rate
m³/min
80
90
100
Power
W
70+70
70+70
70+70
Refrigerant pipe connection
-
Flare-nut connection (factory supplied)
Size
Liquid piping
mm
(in)
Ø9.53
(3/8”)
Ø9.53
(3/8”)
Ø9.53
(3/8”)
Gas piping
mm
(in)
Ø15.88
(5/8”)
Ø15.88
(5/8”)
Ø15.88
(5/8”)
Refrigerant charge
kg
3.90
4.00
4.00
Maximum current
A
18.0
23.0
23.0
Packaging measurements
m³
0.70
0.70
0.70
N O T E
The sound pressure level is based on following conditions:
• 1 meter from the frontal surface of the unit; 1.5 meters from floor level.
•
Voltage of the power source is 230V.
The above data is measured in an anechoic chamber, so reflected sound should be taken into consideration
when installing the unit.