background image

Once power is connected, the red LED on the outside of the box should light up.

If the power is connected without the Door Top Alarm in place, the unit will cycle through the 
following sequence - Power LED (red) comes on and the Status LED will cycle green, amber, 
and red then extinguish. When the pre-set delay time has elapsed, the LED will turn red and 
the internal alarm will sound for approximately 5 seconds. After a total of 20 seconds, the 
unit will return to standby mode.
3.  Staff attack
 

The staff attack is connected into EITHER the Normally Closed OR Normally Open  

 

connectors on the right hand side of the box.

Hipac recommend, where possible, the Normally Closed connections are used as this will 
allow a notification alarm to sound if there is a power failure or wire breakage. In the Normally 
Open connections re used, it may still be possible to obtain a non-audible notification if there 
is a failure e.g. messages appears on nurse’s station display unit. Please consult the Staff 
Attack supplier.
NOTE - The staff attack should not be connected until the Door Top Alarm and Power stages 
have been signed off. (The alarm could go off as the Door Top Alarm has  failsafe system built 
in).
NOTE 2 - All the wiring should be checked and signed off at each stage on the supplied sign 
off sheet during installation by the various contractors. If any problems occur during the 
installation stages, Hipac will not attend site to carry out an investigation without proof that 
all the stages have been signed (or stages up to when the problem has occurred). If Hipac 
attend site and it is proved a stage was signed off in error, this will be chargeable at a day’s 
rate.

Summary of Contents for 120120

Page 1: ...g Information MUST RETURN TO HIPAC 5 Preparing the Door Frame 6 Sign off Sheet MUST RETURN TO HIPAC 7 Wiring Stages Connections 8 Testing Checks 9 Changing of the Alarm delay time 10 Fail safe 11 Fail...

Page 2: ...oor made to measure The solution is available for Non Fire and FD30 fire door application All components are quality checked tested and signed off before dispatch The importance of correct installatio...

Page 3: ...n single swing doors with SECURAHinge please note the below architrave detailing modification is required to allow for the Domed Cap on top of the hinge If new door set it is recommended this is plann...

Page 4: ...Double Action Hinge Fitment Face Fixed Single Rebate Double Rebate Door Type Single Door Double Door Fire Rating Yes No Condition New Door Existing Door Door Handing Refer Diagram Figure 1 or 3 Figur...

Page 5: ...top of the door Bore down 69mm from above at 29mm from the hinged end Meet this bore with another from the hinged side This is a channel for routing the cables Make channel down centerline on the top...

Page 6: ......

Page 7: ...nce Description Overall size t Intumescent Seals Therm A Strip A white phosphate based intumescent compound with self adhesive tape on one side lining the walls and the bottom of the alarm bar rebate...

Page 8: ...s 1 Door Top Alarm 2 Electrically Modified Hinge 3 Cable fed into the ceiling 4 Electronics Box by others electrician or staff attack co 5 Mains Power by others electrician or staff attack co 6 Staff...

Page 9: ...les codes Green Green LED Red Red LED Blue Trigger switch Yellow Common Staff attack wiring Wire to normally closed recommended or normally open Tamper loop Tamper loop Normally closed Alarm contacts...

Page 10: ...to sound if there is a power failure or wire breakage In the Normally Open connections re used it may still be possible to obtain a non audible notification if there is a failure e g messages appears...

Page 11: ...LED will change to Red and the alarm will be registered After approximately 20 seconds the unit will reset itself and the red LED will disappear For risk assessment checks you could go to the orange...

Page 12: ...re message back to say the main control panel at the nurses station The hinge is supplied in 2 pieces the main section of the hinge which takes most of the doors weight and the electrically modified s...

Page 13: ...to the top of the door for a preset period of time between 5 30 seconds this will trigger a relay inside the door top alarm The relay inside will send a signal to our control unit situated out of sig...

Page 14: ...es correct protocol for tamper setting Red LED DTA Alarm signal sent to Staff Attack System After approximately 20 seconds the unit will reset itself and the red LED will disappear The DTA resets but...

Page 15: ...the circuit The DTA control box should be located in the ceiling or a cupboard On the front of this is a red power LED this should be illuminated It this is not lit then there is an issue with your p...

Page 16: ...ak to your staff attack providers to make sure their system is wired correctly Hipac do not need to attend site If the Led doesn t cycle through the colours of green amber red as it should then the sy...

Page 17: ...uctions 1 Fit the Door top alarm to the door 2 Connect the DTA plug and the hinge plug on the side of the hinge which has been profiled with extra holes Ensure the plug is connected in the correct ori...

Page 18: ...the bottom of the EM hinge and the top of the full length hinge are butted together leaving no more than a 0 5mm gap 8 Push the EM hinge section up to within 0 5mm of the top of the frame 9 Mark then...

Reviews: