9
Safety Notes
Measurement categories
To ensure safe operation of measuring instruments, IEC 61010
establishes safety standards for various electrical environments,
categorized as CAT II to CAT IV, and called measurement categories.
DANGER
•
Using a measuring instrument in an environment
designated with a higher-numbered category than
that for which the instrument is rated could result in
a severe accident, and must be carefully avoided.
•
Using a measuring instrument without categories in
an environment designated with the CAT II to CAT
IV category could result in a severe accident, and
must be carefully avoided.
This instrument conforms to the safety requirements for CAT III 1000 V, CAT
IV 600 V measuring instruments.
CAT II:
When directly measuring the electrical outlet receptacles of
the primary electrical circuits in equipment connected to an
AC electrical outlet by a power cord (portable tools, household
appliances, etc.)
CAT III:
When measuring the primary electrical circuits of heavy equipment
(
fi
xed installations) connected directly to the distribution panel,
and feeders from the distribution panel to outlets
CAT IV:
When measuring the circuit from the service drop to the service
entrance, and to the power meter and primary overcurrent
protection device (distribution panel)
T
Outlet
CAT II
Internal wiring
Distribution panel
Service entrance
Service drop
CAT IV
Power meter
CAT III
Fixed installation
See: “2.3 Using Test Leads” (p. 29)
1
Ind.
Appx.
7
6
5
4
3
2
www.
GlobalTestSupply
.com
Find Quality Products Online at: