Measuring Leakage Current
3
Read the current value and frequency.
RMS value of leakage current
Frequency
IMPORTANT
In the following cases, the accurate measurement may not be performed.
•
A large current (around 100 A) flows through adjacent wires.
•
Special waveforms, such as that flowing through the secondary side of the inverter, is measured.
• The jaws are not closed completely.
In particular, if the external dimension of the object under measurement is large, such as when the
instrument is clamped around three-phase wires together in a bundle, make sure that the jaws are closed
completely. If the jaws are even slightly open, errors occur in the measured value and the accuracy
cannot be ensured.
•
The leakage current measurement at zero phase is affected by the load current. For the degree of
influence of the load current, see E12 on p. 82.