4 Start-up
X-DO 12 01
Page 36 of 52
HI 801 023 E Rev. 5.00
4.3.5
Diagnostic Status [DWORD]
Coding of Diagnostic Status
ID
Description
0
Diagnostic values are indicated consecutively.
100
Bit-coded temperature status
0 = normal
Bit0 = 1 : Temperature threshold 1 has been exceeded
Bit1 = 1 : Temperature threshold 2 has been exceeded
Bit2 = 1 : Fault in temperature measurement
101
Measured temperature (10 000 Digit/ °C)
200
Bit-coded voltage status
0 = normal
Bit0 = 1 : L1+ (24 V) is faulty
Bit1 = 1 : L2+ (24 V) is faulty
201
Do not use it!
202
203
300
Comparator 24 V low voltage (BOOL)
1001…1012
Status of channels 1...12
Coding
Description
0x0001
Fault in hardware unit
0x0002
Reset of an I/O bus
0x0008
Hardware Fault
Read back value = 0 with target value = 1
0x0040
Fault (unspecific)
Read back value = 1 with target value = 0
0x0080
Field fault
Read back value = 0 with target value = 1
0x0400
The output cannot be energized:
signals are changing too quickly for relay contacts
0x0800
Fault, test of relay auxiliary contacts.
0x1000
Fault while reading back the status of relay 1
0x2000
Fault while reading back the status of relay 2
0x4000
Limit of switching operations exceeded.
0x8000
The output cannot be energized:
- Read back error
- Contact cleaning
3001…3012
Description of Diag_Value
Coding
Description
0x4000
Test the function of current measuring
0x8000
Read the current
5001...5012
Diagnostic information for each channel about the switching operations
Table 22: Diagnostic Status [DWORD]