X-DO 12 01
3 Product Description
HI 801 023 E Rev. 5.00
Page 25 of 52
3.7
System Cable X-CA 012
The X-CA 012 system cable is used to wire the X-CB 011 03/04 connector board with the field
zone via field termination assemblies.
General
Cable
LIYY 24 x 1.5 mm² +
2 x 2 x 0.14 mm²
Wire
Finely stranded
Average outer diameter (d)
Max. 20 mm for all types of system cables
Minimum bending radius
Fixed laying
Flexible application
5 x d
10 x d
Combustion behavior
Flame resistant and self-extinguishing in
accordance with IEC 60332-1-2, -2-2
Length
8…30 m
Number coding
Color coding
1...24
Color coding based on DIN 47100, see
Table 15.
Table 16: Cable Data
Cable Plug on Connector Board
Cable Plug on FTA
Figure 7: X-CA 12 01 n
The system cable is available in the following standard length:
System cable
Description
Length
X-CA 012 01 8
Cable plugs on both sides
8 m
X-CA 012 01 15
15 m
X-CA 012 01 30
30 m
Table 17: Available System Cables