2 Safety
X-DO 12 01
Page 8 of 52
HI 801 023 E Rev. 5.00
2
Safety
The following safety information, notes and instructions must be strictly observed. The product
may only be used if all guidelines and safety instructions are adhered to.
The use in Ex-Zone is permitted if additional measures are taken.
2.1
Intended Use
HIMax components are designed for assembling safety-related controller systems.
When using the components in the HIMax system, comply with the following general
requirements
2.1.1
Environmental Requirements
Requirement type
Range of Values
Protection class
Protection class II in accordance with IEC/EN 61131-2
Ambient temperature
0...+60 °C
Storage temperature
-40...+85 °C
Pollution
Pollution degree II in accordance with IEC/EN 61131-2
Altitude
< 2000 m
Housing
Standard: IP20
Supply voltage
24 VDC
Table 2:
Environmental Requirements
Exposing the HIMax system to environmental conditions other than those specified in this
manual can cause the HIMax system to malfunction.
2.1.2
ESD Protective Measures
Only personnel with knowledge of ESD protective measures may modify or extend the system
or replace modules.
NOTICE
Device damage due to electrostatic discharge!
When performing the work, make sure that the workspace is free of static and wear
an ESD wrist strap.
If not used, ensure that the device is protected from electrostatic discharge, e.g., by
storing it in its packaging.