4.3.3
Tab: I/O Submodule DO12_01: Channels
Tab: I/O Submodule DO12_01: Channels contains the following system parameters for each
digital output.
Global variables can be assigned to the statuses and parameters with -> and used in the user
program. The value without -> must be directly entered.
Name
Data type
R/W
Description
Channel no.
---
R
Channel number, defined by default
Channel value
[BOOL] ->
BOOL
R
Binary value in accordance with the switching level LOW (dig)
and HIGH (dig).
TRUE: Channel energized
FALSE: Channel de-energized
-> Channel OK
BOOL
R
TRUE: Faultless channel
The channel value is valid.
FALSE: Faulty channel
The channel is de-energized
-> Channel current
[DINT]
DINT
R
Measured channel current (10 000 digits/mA)
Range of values 0…50 000 000
Redund.
BOOL
W
Requirement: A redundant module must be configured.
Activated: Activate the channel redundancy for this channel
Deactivated: Deactivate the channel redundancy for this
channel
Default setting: Deactivated
Table 20: Tab: I/O Submodule DO12_01: Channels in the Hardware Editor
4.3.4
Submodule State [DWORD]
Coding of Submodule State
Coding
Description
0x00000001
Fault in hardware unit (submodule).
0x00000002
Reset of an I/O bus
0x00000004
Faults detected while configuring the hardware
0x00000008
Fault detected while verifying the coefficients
0x00000080
Reset of CS monitoring (Chip Select monitoring)
0x20000000
Warning about inaccurate current measuring
0x40000000
Error while reading back the relay voltage
0x80000000
Error while reading back the safety switch status
Table 21: Submodule Status [DWORD]