3 Product Description
X-DO 12 01
Page 18 of 52
HI 801 023 E Rev. 5.00
Relay Outputs
Number of outputs (channels)
12, potential-free
Total switching current (all channels)
max. 30 A
Switching voltage
5...250 V
Switching current per channel
5 mA...4 A
Switching frequency
max. 4 Hz
Switching time
(energized contact closed)
10 ms
Reset time (de-energized contact
closed, without wiring)
3 ms
Bounce time for the energized contact
2 ms
Contact material
0.2…0.4 µm Au
Product life
Mechanical
Electrical
≥ 10 x
10
6
switching operations
≥ 2.5 x 10
5
switching operations with ohmic full load
Table 8:
Data of the Relay Outputs
Default
applications
Default
applications
Burner applications
in accordance with
VDE 0116, EN 50156
Switching operations
< 100 000
< 250 000
< 250 000
Switching capacity
DC
(non-inductive)
≤ 30 VDC
max. 4.00 A
max. 4.00 A
Fuse: 3.15 A
≤ 70 VDC
max. 1.25 A
max. 1.25 A
Fuse: 0.63 A
≤ 127 VDC
max. 0.50 A
max. 0.50 A
Fuse: 0.315 A
≤ 250 VDC
max. 0.28 A
max. 0.25 A
Fuse: 0.125 A
Switching capacity
DC
(inductive load
tau = L/R =
40 ms)
≤ 30 VDC
max. 0.80 A
max. 0.50 A
Fuse: 0.315 A
≤ 70 VDC
max. 0.32 A
max. 0.20 A
Fuse: 0.125 A
≤ 127 VDC
max. 0.19 A
max. 0.12 A
Fuse: 0.063 A
≤ 250 VDC
max. 0.10 A
max. 0.06 A
Not specified
Switching capacity
AC
(non-inductive)
≤ 125 VAC
max. 4.00 A
max. 3.00 A
Fuse: 1.25 A
≤ 250 VAC
max. 4.00 A
max. 1.50 A
Fuse: 0.63 A
Switching capacity
AC
cos φ > 0.5
≤ 125 VAC
max. 3.00 A
max. 1.20 A
Fuse: 0.63 A
≤ 250 VAC
max. 1.50 A
max. 0.60 A
Fuse: 0.315 A
Table 9:
Currents and Fuses
The table contains fuse values for burner applications and permissible maximum values for
standard applications.
Fuse protection is mandatory for burner application contact circuits and HIMA strongly
recommends employing fuse protection in standard applications.