Communication
97/154
10.1.3
Connections 8 to 10
Input process data
The following table gives a description of the process data structure of the
input process data and is valid for connection 8, connection 9 and
connection 10.
Byte
Number
of bytes
Input process data
Description
1
1 byte
DI status
Reserved
2
1 byte
Padding byte
Do not use
3 … 4
2 byte
DI data
Reserved
5
1 byte
WP01 data status
6
1 byte
Padding byte
Do not use
7 … 10
4 byte
WP01 process input data
IO-Link input data of the IO-Link Device wireless
connected to WP01. For a description of the data,
see manual of the manufacturer of the used IO-Link
Device.
11
1 byte
WP02 data status
12
1 byte
Padding byte
Do not use
13 … 16
4 byte
WP02 process input data
IO-Link input data of the IO-Link Device wireless
connected to WP02. For a description of the data,
see manual of the manufacturer of the used IO-Link
Device.
17
1 byte
WP03 data status
18
1 byte
Padding byte
Do not use
19 … 22
4 byte
WP03 process input data
IO-Link input data of the IO-Link Device wireless
connected to WP03. For a description of the data,
see manual of the manufacturer of the used IO-Link
Device.
23
1 byte
WP04 data status
24
1 byte
Padding byte
Do not use
25 … 28
4 byte
WP04 process input data
IO-Link input data of the IO-Link Device wireless
connected to WP04. For a description of the data,
see manual of the manufacturer of the used IO-Link
Device.
29
1 byte
WP05 data status
30
1 byte
Padding byte
Do not use
31 … 34
4 byte
WP05 process input data
IO-Link input data of the IO-Link Device wireless
connected to WP05. For a description of the data,
see manual of the manufacturer of the used IO-Link
Device.
35
1 byte
WP06 data status
36
1 byte
Padding byte
Do not use
37… 40
4 byte
WP06 process input data
IO-Link input data of the IO-Link Device wireless
connected to WP06. For a description of the data,
see manual of the manufacturer of the used IO-Link
Device.
38
1 byte
WP07 data status
39
1 byte
Padding byte
Do not use
40 … 46
4 byte
WP07 process input data
IO-Link input data of the IO-Link Device wireless
connected to WP07. For a description of the data,
see manual of the manufacturer of the used IO-Link
Device.
47
1 byte
WP08 data status
48
1 byte
Padding byte
Do not use
NFD-3090-EIS-IOLM\W | Hardware, installation and commissioning
DOC200701UM02EN | Revision 2 | English | 2021-08 | Released | Public
© Hilscher 2020 - 2021