Configuration
50/154
Write access to IO-Link Wireless Master device
To write data to the IO-Link Wireless Master device, proceed as follows:
Ø
Enter the
PortId
of the IO-Link Wireless Master that you want to
access as a hexadecimal value in the
PortId
entry field.
Ø
Enter the
ArgBlockId
of the connected IO-Link Device that you want
to access as a hexadecimal value in the
ArgBlockId
entry field. The
default value here is
00
.
Ê
In case of input errors, an error message appears.
Ø
Enter the data to be written (in hexadecimal, without spaces, e.g.,
0102030405) in the
ArgBlockData
entry field.
Write example: PortId = 01, ArgBlockId = B090, ArgBlockData = 01020304
Ø
Click on
Write
.
Ê
The write access is performed.
If the execution was successful, the text
Write ok:
and the result is
displayed in the history. The entries in the history then have the following
structure:
Time - PortId:ArgBlockId - Write ok: <Result>
If the execution was not successful, an error message with error codes of
the IO-Link Wireless Master and IO-Link Device is displayed in the history.
The entries in the history then have the following structure:
Time - PortId:ArgBlockId:Data - Write failed:
IOLMErrorCode(<error code of the IO-Link master>):
IOLDErrorCode(<error code of the IO-Link Device>)
Delete the history of read and write accesses
To clear the logged history of read and write accesses:
Ø
Click
Clear history
.
ð
The history of read and write accesses is deleted.
NFD-3090-EIS-IOLM\W | Hardware, installation and commissioning
DOC200701UM02EN | Revision 2 | English | 2021-08 | Released | Public