Video Security Control Panel User Manual
--140-
-
Q: How to solve the problem of two LED keypad address being same?
A:
When two LED keypad addresses are the same, the situation of two keypads demanding bus communication at
the same time will appear and cause conflict. The only solution is to remove one keypad and reset the other
keypad to an unused legal address. Restore the control panel by processing program code ({Operator
Password}{*}{6}{8}{#})
Q: Why there is no Disarming Report?
A:
To make sure the user has permission of
Disarming Report, please refer to
Operator Settings.
Q: What to do if the user cannot disarm after arming the system?
A:
There are two different situations:
1.
The user does not have permission to disarm, please contact the administrator.
2.
Take the follow instructions when there is only one user in the system without permission to disarm;
1)
Initialize the hardware, restore the password of operator, main operator password and
permission, and then disarm with main operator. The initialization password of operator is:
012345, the initialization password of main operator is: 1234, the permission is: arm/disarm.
There is arm/disarm report and bypass is permitted. Please refer to FAQ of hardware
initialization for more information about hardware initialization.
2)
The command code to restore factory parameters: {Password of operator} + {*} + {8} + {9} +
{#}.
This method is not recommended because it will initialize all Programming contents.
Q: How to do the hardware initialization?
A:
Video security control panel hardware initialization only initializes operator password: 012345 and main
operator password: 1234, main operator permission is arm/disarm. There are arming/disarming report and allows
bypass.
Steps:
1)
Power off the video security control panel and open the cover;
2)
Short the restore switch of the control panel with shorting nut or connection cables;
3)
Power on the control panel and power off it 10s later;
4)
Please remove the shorting nut or connection cable on the restore switch;
5)
Cover the control panel well;
6)
Recharge the control panel;
Q: Why is there no response for keypad operational order but alert sound of error 10s later?
A:
It may be caused by follow situations:
1)
Poor contact of the connection cable between LED keypad and the control panel, please check
if the cable is normal;