IC100CX SERVICE MANUAL
Manual IC100CX GB
Page 16 di 20
FA12
Proportional band in summer
0.0
0
0.0
0
25.0
45
50.0
725
°C
°F
Bar
Psi
Decimal
integer
Decimal
Integer
FA13
CUT-OFF differential in summer
0.0
0
0.0
0
25.0
45
50.0
725
°C
°F
Bar
Psi
Decimal
integer
Decimal
integer
FA14
Override CUT-OFF in summer
0.0
0
0.0
0
25.0
45
50.0
725
°C
°F
Bar
Psi
Decimal
integer
Decimal
integer
FA15
Delay time for CUT-OFF
0
250 Sec
FA16
Fan speed in summer night function
30
100 %
FA17
Minimum fan speed in winter
30
100 %
FA18
Maximum fan speed in winter
30
100 %
FA19
Temperature / pressure setpoint for minimum speed in winter
-50.0
-58
0.0
0
110
230
50
725
°C
°F
Bar
Psi
Decimal
integer
Decimal
integer
FA20
Temperature / pressure setpoint for maximum speed in winter
-50.0
-58
0.0
0
110
230
50
725
°C
°F
Bar
Psi
Decimal
integer
Decimal
integer
FA21
Proportional band in winter
0.0
0
0.0
0
25.0
45
50.0
725
°C
°F
Bar
Psi
Decimal
integer
Decimal
integer
FA22
CUT-OFF differential in winter
0.0
0
0.0
0
25.0
45
50.0
725
°C
°F
Bar
Psi
Decimal
integer
Decimal
integer
FA23
Override CUT-OFF in winter
0.0
0
0.0
0
25.0
45
50.0
725
°C
°F
Bar
Psi
Decimal
integer
Decimal
integer
FA24
Fan speed in winter night function
30
100 %
Hot Start Function
Parameter
Description
Min
Max
Meas.
Resolution
FA25
Hot Start Setpoint
-50.0
-58
110
230
°C
°F
Decimal
integer
FA26
Hot Start differential
0.1
0
25.0
45
°C
°F
Decimal
integer
Pr2
Password
0
999
Anti-freeze / Heater parameters
Parameter
Description
Min
Max
Meas.
Resolution
Ar01
Minimum value of Anti-Freeze Setpoint
-50.0
-58
Ar03
°C
°F
Decimal
integer
Ar02
Maximum value of Anti-Freeze Setpoint
Ar03
110
230
°C
°F
Decimal
integer
Ar03
Anti-freeze Setpoint in chiller mode
Ar01
Ar02 °C/°F Dec/int
Ar04
Anti-Freeze Differential in chiller mode
0
0
25.0
45
°C
°F
Decimal
integer
Ar05
Anti-Freeze alarm delay
0
250 Sec
Ar06
Maximum number of Anti-Freeze alarm events in 1 hour
0
16
Ar07
Anti-Freeze alarm delay after starting in Heat Pump
0
250 Sec
Ar08
Anti-Freeze Setpoint of the electrical heater in Chiller mode
-50.0
-58
110
230
°C
°F
Decimal
integer
Ar09
Anti-Freeze Setpoint of the electrical heater in Heat Pump mode
-50.0
-58
110
230
°C
°F
Decimal
integer
Ar10
Anti-Freeze Setpoint of external electrical heater (water/water units)
-50.0
-58
110
230
°C
°F
Decimal
integer
Ar11
Anti-Freeze Differential in Chiller
0.1
0
25.0
45
°C
°F
Decimal
integer
Ar12
Anti-Freeze Differential in Heat Pump
0.1
0
25.0
45
°C
°F
Decimal
integer
Ar13
Anti-freeze electrical heater regulation
0= enabled during regulation control
1= enabled active during regulation an defrost
0
1