IC100CX SERVICE MANUAL
Manual IC100CX GB
Page 19 di 20
AL19
Allows to choose the probe for the anti- freezer heater alarm.
0= Relative to Ar16 parameters in chiller mode - Ar17 in hp.
1= on Pb1 probe
2= on Pb2 probe
3= on Pb3 probe
4= on Pb4 probe
0
4
AL20
Maximum number of general unit block alarm interventions per hour
0
16
AL21
General alarm delay starting from digital input activation
0
250 Sec
AL22
Delay to reset the general alarm starting from digital input de-activation
0
250 10
sec
10 sec
AL23
General alarm type:
0 = signaling only does not depend on AL20 (alarm relay and buzzer enabled), always reset automatically
1= the alarm blocks the unit; resetting of the alarm depends on the value of the AL20 parameter
0
1
AL24
System’s inlet water high temperature alarm set point
-50.0
-58
110
230
°C
°F
Dec
int
AL25
System’s inlet water high temperature alarm differential
0.1
0
25.0
45
°C
°F
Dec
int
AL26
Delay time for signaling the system’s inlet water high temperature alarm
0
250 10
sec
10 sec
AL27
Maximum number of system inlet high temperature alarm interventions per hour
0
16
AL28
Condenser water flow alarm delay time
0
250 Sec
AL29
Maximum duration of the flow switch alarm before it becomes manual and blocks the water pump
0
250 Sec
AL30
Minimum activation time for water flow alarm
0
250 Sec
AL31
Minimum time with inactive water flow input (after alarm event).
0
250 Sec
AL32
Condenser flow switch alarm configuration
0= not used
1= activated only in chiller mode
2= activated only in h.p. mode
3= activated in chiller and h.p. mode
0
3
Pr2
Password
0
999
1.
C
ONNECTING
D
IAGRAM
1.1
Model with 5 internal relays and 1 modulating output (0..10V or 4..20mA)
MF ID1, MF ID2, MF ID5 = multifunction digital inputs
ID3 = high pressure digital input
ID4 = low pressure digital input
RL1 = compressor relay
MF RL2, MF RL3, MF RL4, MF RL5 = multifunction relays
MF o.c. out = multifunction open collector output (for external relay)
Pb1, Pb2, Pb3, Pb4 = NTC probe or digital input
Tk = output for external fan speed controller
Analog output = output 0..10V / 4..20mA for external fan speed module (for condenser fan or modulating evaporator
water pump)
1.2
Model with triac on board and ratiometric pressure trasducer (Pb3)
MF ID1, MF ID2, MF ID5 = multifunction digital inputs