IC100CX SERVICE MANUAL
Manual IC100CX GB
Page 14 di 20
CF47
Remote keyboard: visualization in Std-by mode
0 = default visualization (CF36 and CF43 parameters)
1 = the display visualizes “OFF”
2 = the display visualizes “StbY”
0
2
CF48
Analog output configuration
0 = 4..20mA
1 = 0..10V
0
1
Pr2
Password value
0
999
Dynamic Setpoint
Parameter
Description
Min
Max
Meas
Resolution
Sd01
Dynamic Setpoint
0= Not enabled
1= Enabled
0
1
Sd02
Maximum summer dynamic Offset
- 30.0
-54
30.0
54
°C
°F
Decimal
integer
Sd03
Maximum winter dynamic Offset
- 30.0
-54
30.0
54
°C
°F
Decimal
integer
Sd04
External air d. setpoint during summer
-50.0
-58
110
230
°C
°F
Decimal
integer
Sd05
External air d. setpoint during winter
-50.0
-58
110
230
°C
°F
Decimal
integer
Sd06
External air differential during summer
- 30.0
-54
30.0
54
°C
°F
Decimal
integer
Sd07
External air differential during winter
- 30.0
-54
30.0
54
°C
°F
Decimal
integer
Pr2
Password value
0
999
Energy Saving
Parameter
Description
Min
Max
Meas
Resolution
ES01
Energy saving starting hour (0÷24)
0
23.50 Min 10
Min
ES02
Energy saving ending hour (0÷24)
0
23.50 Min 10
Min
ES03…ES09 Monday…Sunday
0 = Not enabled
1= Enabled
0
1
ES10
Energy saving setpoint offset in chiller
-30.0
-54
30.0
54
°C
°F
Decimal
integer
ES11
Energy saving differential in chiller
0.1
0
25.0
45
°C
°F
Decimal
integer
ES12
Energy saving setpoint offset in heat pump
-30.0
-54
30.0
54
°C
°F
Decimal
integer
ES13
Energy saving differential in heat pump
0.1
0
25.0
45
°C
°F
Decimal
integer
Pr2
Password value
0
999
Compressor parameters
Parameter
Description
Min
Max
Meas.
Resolution
CO01
Minimum ON time
0
250 Sec
10Sec
CO02
Minimum OFF time
0
250 Sec
10Sec
CO03
ON delay time between two compressors or Comp. and valve
1
250 Sec
CO04
OFF delay time between two compressors or Comp. and valve
0
250 Sec
CO05
Output time delay after power supply start-up
0
250 Sec
10Sec
CO06
Compressor On delay time after Pump/”Supply fan” activation
1
250 Sec
CO07
Compressor OFF delay time after Pump/”Supply fan” de-activation
0
250 Sec
CO08
Compressor rotating control
0= Enabled
1= Fixed sequence
0
1
CO09
Time delay for solenoid valve of water side
0
250
Sec
CO10
Stage vale polarity
0= Capacity stage ON
1= Capacity stage OFF
0
1
CO11
Water pump / Supply fan operating mode
0= Not used
1= Always on (ON/OFF output)
2= ON if the compressor is on (ON/OFF output)
3= Always on (4
20mA output)
4= ON if compressor is ON (4
20mA output)
0
4
CO12
Compressor 1
0 = Enabled
1 = OFF
0
1
CO13
Compressor 2 / Stage valve.
0 = Enabled
1= OFF
0
1
CO14
Hour counter setpoint for 1
st
compressor 0
999 Hr 10
Hr
CO15
Hour counter setpoint for 2
nd
compressor 0
999 Hr 10
Hr
CO16
Hour counter setpoint for pump/”Supply fan”
0
999 Hr 10
Hr
Unloading evaporator
CO17
Unloading set point (evaporator side)
-50.0
-58
110
230
°C
°F
Dec
int