IC100CX SERVICE MANUAL
Manual IC100CX GB
Page 11 di 20
CF09
ID2 configuration
0= 1
st
compressor thermal protection
1= Condenser fan thermal protection
2= Evaporator flow switch alarm
3= Remote On/off
4= Cooling/Heating
5= 2
nd
compressor thermal protection
6= 2
nd
compressor or step request (Motocondensing unit)
7= End defrost
8= Energy Saving
9= Anti Freeze alarm
10= 1
st
and 2
nd
compressor thermal protection
11= General alarm for total unit shutdown
12= Evaporator water pump thermal protection alarm/ supply fan thermal protection alarm
13= Condenser water pump thermal protection alarm
14= Condenser flow switch alarm
15= not used
0
15
CF10
ID5 configuration
0= 1
st
compressor thermal protection
1= Condenser fan thermal protection
2= Evaporator flow switch alarm
3= Remote On/off
4= Cooling/Heating
5= 2
nd
compressor thermal protection
6= 2
nd
compressor or step request (Motocondensing unit)
7= End defrost
8= Energy Saving
9= Anti Freeze alarm
10= 1
st
and 2
nd
compressor thermal protection
11= General alarm for total unit shutdown
12= Evaporator water pump thermal protection alarm/ supply fan thermal protection alarm
13= Condenser water pump thermal protection alarm
14= Condenser flow switch alarm
15= not used
0
15
CF11
Pb4 configuration in digital input mode
0= 1
st
compressor thermal protection
1= Condenser fan thermal protection
2= Evaporator flow switch alarm
3= Remote On/off
4= Cooling/Heating
5= 2
nd
compressor thermal protection
6= 2
nd
compressor or step request (Motocondensing unit)
7= End defrost
8= Energy Saving
9= Anti Freeze alarm
10= 1
st
and 2
nd
compressor thermal protection
11= General alarm for total unit shutdown
12= Evaporator water pump thermal protection alarm/ supply fan thermal protection alarm
13= Condenser water pump thermal protection alarm
14= Condenser flow switch alarm
15= not used
0
15
CF12
ID1 input polarity
0= active for closed contact
1= active for open contact
0
1
CF13
ID2 input polarity
0= active for closed contact
1= active for open contact
0
1
CF14
ID3 input polarity
0= active for closed contact
1= active for open contact
0
1
CF15
ID4 input polarity
0= active for closed contact
1= active for open contact
0
1
CF16
ID5 input polarity
0= active for closed contact
1= active for open contact
0
1
CF17
Pb1 input polarity
0= active for closed contact
1= active for open contact
0
1
CF18
Pb2 input polarity
0= active for closed contact
1= active for open contact
0
1
CF19
Pb4 input polarity
0= active for closed contact
1= active for open contact
0
1