background image

650.65-N2 

Turn  the  electrical  and  gas  supplies  back  on,  and  with  the 
burners  in operation,  check  for gas  leakage  around  the  plug 

with a soap and water solution. 

ADJUSTMENT 

OF 

PRIMARY AIR 

The main burners should be in operation for 15 minutes before 

making  the  primary  air  adjustment.  The  burner  flame  should 

not  contain  any  yellow  color  (Refer  to  Figure  13).  With  the 
furnace  operating  al  full  input,  adjust  the  primary·air  of  the 

burners as  follows: 

COMBUSTION AIR INTAKE 

BURNER 

BURNER 
FLAME 

RGURE 

1 3-

PROPER FLAME APPEARANCE 

CAUTION: 

The  front  panel of the burner  enclosure  must 

be 

in 

place  and  secured  with  screws  during  normal  operation 

and  when  observing  the proper burner  flame. 

Natural  Gas  or  Propane  (LP) 

All  models  are  shipped with the  air shutters  wide  open.  Local 

variations in the gas supply may require changes in the settings 

described  above.  To  change  the  air  shutter  settings,  use  the 

following procedure: 

1. 

Remove  the front access door.· 

2. 

Turn off  all power to  the  unit and remove  the  front door  of 

the burner box. 

3.  Rotate  the  burners  until  the  air  �hutter  locking  screw  is 

facing downward. 

4. 

Adjust the air shutters with the power to the unit "OFF"  and 

retighten the  locking screws. 

5.  Re-install  the  front door of the  burner 

box 

and  tighten  the 

screws which secure the door. 

6. 

Restore  power  and  start  the  unit.  Observe  through  the 

observation port  to  see if all flames are now  blue in  color. 

If  yellow flames  are still  visible,  repeat steps 

thru 

6. 

7.  Cycle the burners on an off a few times to verify the burners 

are lighting  promptly  and  properly 

8. 

Replace  front access  door. 

CHECKING GAS  INP U T  (NATURAL GAS) 

NOTE: 

Front  door of burner box must 

be 

secured when check­

ing gas input. 

1. 

T urn  off  all  other  gas  appliances  connected  to  the  gas 

meter. 

2. 

With the furnace  turned on,  measure the time needed  for 

one  revolution  of  the  hand  on  the  smallest  dial  on  the 
meter.  A typical domestic gas meter usually has a 

1/2 

or 

cubic foot test  dial. 

3. 

Using the  number  of  seconds  for  each revolution and  the 

size  of  the  test  dial  increment,  find  the  cubic  feet  of  gas 

• 

,.-_ 

I"") 

TABLE  3 

GAS  RATE  (CUBIC  FEET PER HOUR) 

Seconds  for 

Size  of Test  Dial 

one  RevoL 

1/2 

cu. 

ft. 

cu. 

ft. 

10 

180 

360 

12 

150 

300 

14 

129 

257 

16 

113 

225 

18 

100 

200 

20 

90 

180 

22 

82 

164 

24 

75 

150 

26 

69 

138 

28 

64 

129 

30 

60 

120 

32 

56 

113 

34 

53 

106 

36 

50 

100 

47 

95 

40 

45 

90 

42 

43 

44 

4 1  

82 

46 

39 

78 

37 

75 

50 

36 

72 

52 

35 

69 

54 

34 

67 

56 

32 

64 

58 

3 1  

6 2  

60 

-

30 

60 

NOTE: 

To find the Btuh input,  multiply the number of cubic  feet 

of gas consumed  per hour by the BTU content of the gas 
in  your  particular  locality.  Contact  your  gas  company  for 

this information,  as it  varies widely from  city to city. 

EXAMPLE: It is found by measurement that it takes 

26 

seconds 

for the hand on the 

cubic  foot dial to make a revolution with 

only  a 

120,000 

Btuh  furnace  running. Using this information 

locate 

26 

seconds in  the  first  column of Table 

3. 

Read acros

� 

to the column headed 

"1 

cubic foot• where you will see that 

138 

cubic feet of  gas per hour are  consumed by the furnace at that 

rate.  Multiply  138  by 

850 

(the  BTU  rating  of the  gas obtained 

from the local gas company).  T he result is 117,300 Btuh, which 

is close to the 

120,000 

Btuh  rating of the  furnace. 

If  the  actual  input  is  not  within 

5% 

of  the  furnace  rating,  with 

allowance 

be 

in§  made  for  the  permissible range-of the regula· 

tor  setting  (  0.3  inches  W.C.),  replace  the  orifice  spuds  with 
spuds  of the proper size. 

CAUTION: 

Be  sure  to  relight  any  gas  appliances  that  were 

tumed off at the start of this input check. 

ADJUSTMENT 

OF 

TEMPERATURE RISE 

The  temperature  rise,  or  temperature  difference  between  the 

return  air and  the  heated  air  from  the  furnace,  must 

be 

within 

the  range  shown  on  the  furnace  rating  plate  and  within  the 
application limitations  shown in Table  1. After the  temperature 
rise has been determined,  the cfm can be calculated. 

After  about 

20 

minutes  of  operation,  determine  the  furnace 

temperature  rise.  Take readings of both the return air and the 

h�"'"rl 

in  thr>  rl•  wt�  :::.hrHit  �i"" 

IPP.I 

from  th�  fumac� 

where 

Summary of Contents for PBNU-LD06N040

Page 1: ...th low NOx mlss 9ns o 35 nanograms joule 100 shut off main gas valve for extra safety Propane modet convertible to natural gas PSG multlpte speed direct dove mJtor with large quiet blower 24V 40 VA co...

Page 2: ...g Extinguish any open flames Immediately call your gas supplier from a neighbor s phone Folio the gas sup plier s instructions If you cannot reach your gas supplier call the fire department 035 10976...

Page 3: ...are not handled property CAUTION The cooling coil must be installed in the supply air Condensate Piping 9 Electrical Data 9 Electrical Connections 9 10 Safety Controls 10 Start Up Adjustments 10 11 I...

Page 4: ...water codes and other applicable codes CAUTION Do notinstall the furnace in an unconditioned space or garage that could experience ambient temperatures of 3Z F 0 8 or lower CAUTION This unit must be...

Page 5: ...ia K O CAS INLcr f tr l 114 x VENT OOTLET 3 dia K O 2 8 1 2 LEFT SIDE 2 7 16 _ c D 11 2 15 2 15 2 21 2 21 3 21 3 21 3 25 3 Blower Max Outlet Temp HP Size OF 175 1 5 9 4 175 113 1 6 175 1 2 11 8 175 1...

Page 6: ...ere vent gas coutd enter the building 1 foot Above grade and anticipated snow depth 1 foot Above rade when adjacent to a publtc walkway _ 7 feet From electric gas meters regulators and rehef equipll e...

Page 7: ...his procedure To remove a filter from the side location push the closed end of the filter retainer down until it clears the flange on the side panel which acts as a catch for the retainer When the ret...

Page 8: ...s including pilots Do not breatht vapors and avoid contact with skin and eyes 6 All joints must be made to provide a permanent air tight water tight seal The only exception to this means o joining is...

Page 9: ...ame color as the building to make them less noticeable RGURE 6 ROOFTOP TERMINATION If optional side walt venting is to be used installation of the terminal kit should be as shown in Figures 7 and 8 Th...

Page 10: ...ocedure for condensate piping is as follows 1 Determine whether the condensate drain line will be in stalled through the right or left side of he furnace Unitary Products Group 650 65 N2 2 Carefully r...

Page 11: ...rminal board on the low voltage transformer Typical control wiring is shown in Figure 1OA Set the heat anticipator in t he room thermostat to 1 16 amps Setting it lower will cause short cycles Setting...

Page 12: ...surface igniter to begin glowing c If glow is seen turn the thermostat down below room temperature Hot surface igniter should stop glowing 3 Tum the gas supply ON at external valve and main gas valve...

Page 13: ...lly has a 1 2 or 1 cubic foot test dial 3 Using the number of seconds for each revolution and the size of the test dial increment find the cubic feet of gas t _ L L I TABLE 3 GAS RATE CUBIC FEET PER H...

Page 14: ...lay 3R which energizes the venter When the proper amount of combustion air is being provided a pressure switch activates the SOE47 ignition control A sec ond and third pressure switch 2LP or 3LP and 4...

Page 15: ...xchanger 1 Turn off the main manual gas valve extern to the furnace 2 Turn off the electrical power to the furnace 4 Disconnect the gas supply piping and control wiring from the gas valve 5 Remove the...

Page 16: ...rain trap has been emptied during this cleaning procedure refill it by following the instructions foundin the start Up andAdjustment section on this instruction 650 65 N2 13 Operate the unit for a min...

Page 17: ...2Jl Jl llP 2L lrS 1IIP TS IS IP 0 rn 6 o R lllm E Lilt lUI CN ICITCJl flUY II 1 M R I TOO flUY CDC flUr rrCJl ttJTm W TT 1l lflTOl IX Oll SWITOi SYI I Ol lltOit T ROO 24 110 i vtRIte tt1 LOO 115 X T I...

Page 18: ...ffi l l KJTrn B FETf NITG UXXli l l tlTG l tITGl F fl JRR fl ilTD 1 ocx KETI PllXl 24 YQT V RII ll ro J E TI PlLO liS VQT r AII ll ro xE1 Tarf 2 VIIS YQT lim ro xFTI PlLO 1 EtilTCJI Iill Tl COifFa a m...

Page 19: ...ansformer thermostat controller and wiring Place jumper on Place jumper pressure switch 1 LP on relay 3R Replace I between C NC between 1 3 venter Venter Okay Venter Okay YES YES r Check hoses connect...

Reviews: