background image

Fusible  Unk Control 

This  control  is  mounted  in  the  burner  compartment.  If  the 

temperature  in  the  burner  compartment  exceeds  306°F,  the 

cir?ui.t to the ig.niter control and the gas valve is de-energized. 

Th1s  1s·a one-t1me fusible link  type  control.  Before  the furnace 

can operate again, the control must 

be 

replaced. The operation 

of this control indicates  a possible  burner  flame  r<?ltout. condi­

tion.  The  combustion  air blower and the  combustion  a1r pres­

sure  switch should be checked for proper operation. 

Pressure Switches 

This furnacels supplied with pressure switches which monitor 

the flow through ths-combustion air/vent 

system. These 

switches  de-energize the  ignition control 

and  the  gas 

valve if any of the following conditions are present. 

1.  Blockage  of combustion air piping or terminal. 

2. 

Blockage  of vent piping or terminal. 

3.  Failure of combustion  air  blower motor. 

4. 

Blockage  of  condensate  drain piping. 

START-UP  AND ADJUSTMENTS 

The  initial  start-up  of  the  furnace  requires  the  following addi­

tional procedures: 

1.  When the  gas  supply  is' initially connected to  the furnace, 

the gas piping  may be full of air.  In order to purge this air, 
it is recommended that the ground union be loosened until 
the odor of  gas is detected. When gas is detected,  imme­

diately  retighten the union  and check for leaks.  Allow five 

minutes for any gas to dissipate before continuing with the 

start-up  procedure. 

WARNING: 

Be sure proper ventilation is available to dilute and 

carry  away  any vented  gas. 

2. 

The  condensate  trap  must 

be 

filled  with  water  before 

putting  the  furnace  into  operation.  The  recommended 
procedure is as follows: 

a  Disconnect  the  condensate  drain  hose  from  the  con­

densate  drain  outlet fitting  (see  Figure  10  for location 

of this hose  connection). 

b.  Elevate  this  hose  above  trap  level  and  fill  with water 

using a funnel.  Drain excess water into a  container. 

c.  Replace  the condensate drain hose  and clamps. 

3. 

All  electrical 'connections  made  in  the  field  and  in  the 

factory should 

bEi 

checked for proper tightness. 

IGNITION SYSTEM CHECKOUT/ADJUSTMENT 

1.  Tum  gas  supply  OFF  at external  gas  valve  or  main  gas 

valve  (see  F.igure 

12). 

Turnelectrical  power 

ON. 

Check 

that 

24 

volts  is  available  across terminal C  and 

on  the 

transformer. 

2.  Check ignition  module operation as follows: 

a.  Set the  thermostat  to  "heat".  Tum  thermostat  setting 

above  room temperature to call for hea1. 

b .. Through burner box observation ports watch-for the hot 

surface igniter to  begin glowing. 

c.  If glow is  seen,  turn the thermostat down  (below room 

temperature).  Hot surface igniter should stop glowing. 

3.  Tum the gas supply ON at external valve and main gas valve. 

4. 

Set the-thermostat above room temperature to call for h

ea

t

.

SystE)m  �tart-Lip will occur 

as 

follows: 

Unitary Producls Group 

650  65-N2 

a.  Venter  motor  will 

start  and 

come  up  to speed.  Sh ortly 

after venter 

start-up,  the hot suriace igniter  will  glow 

for 

about 

45 

seconds. 

b.  After  warm-up 

cycle,  ignition  m

od

u

le  will  energize 

(open) the 

ma1n gas 

valve for four seconds. 

At  the same 

t

i

m

e power 

to 

the igniter is  shut otf . 

NOTE: 

Burner ignition  may not  be satisfactory on first  start-up 

due  to residual air  in gas  line,  or until gas  pressure 

{mani­

fold}  or  burner  air  shutters  are  adjusted. 

6.  With furnace  in  operation,  paint the 

pipe joints 

and  valve 

gasket  lines  with  a  rich soap 

and 

water··solution.  Bubble 

indicate  a  gas  leak.  Take  appropriate  steps  to 

stop 

the 

leaks.  If the leak persists, replace the co

mp

on

e

n:

WARNING: 

DO  NOT  omit  this  test! 

NEVER 

use 

a  flame 

to 

check  for  gas  leaks. 

ADJUSTMENT  OF MANIFOLD 

G

AS P RESS

URE 

1. 

Tum gas off at main gas valve. Remove  1/8" plug in the main 
gas valve body  and install proper manometer tube  adapter 
fitting. Connect line 

from 

gas valve tap to manometer 

2. 

Refer to Figure  12 for location of pressure regulator adjust­

ment cap and screw on  main gas valve. 

Inlet 

Wrench 

Wiring 

Terminals 

Jumper 

Boss 

Manual Gas 

Press. Reg. 

Control Knob  Under Cover 

Screw 

FIGURE 

12- GAS  VALVE 

Outlet 

Pressure 

Tap 

NOTE: 

The screw-off 

cap 

for  the  pressure  regulator must 

be 

re­

moved 

entirely to gain access to 

the 

adjustment 

screw 

Loosc:n­

ing or tifjltening the 

cap cbes 

not adjust the 

flow 

of gas. 

3. 

Turn  gas  and  electrical  supplies 

ON. 

Start  furnace  and 

observe manifold pressure on manometer. 

4. 

Adjust  manifold pressure  by  adjusting gas  valve reg'u.!ator 

screw:  for natural gas,  set  at 3.5"  W.C.;  for  propane 

{LP) 

gas,  set at 10.0"  W.C. 

If  gas  valve  regulator  is  turned  in,  or  clockwise,  manifold 

pressure  is  increased.  If screw  is  turned  out,  or  counter­
clockwise,  manifold pressure will decrease. 

Natural Gas 

3.5"  w.c. 

10.0"  w.c. 

WARNING: 

If  manifold  pressure  is  too  high,  an over-fire  con-

_, 

dition exists  which  could  cause  heat  exchanger failure.  If 
the  manifold  pressure  is  too  low,  sooting  and  eventual 
clogging of  the heat exchanger  could occur. 

WARNING: 

Once the correct gas  pressure  to  the  burners  has 

been established,  tum the gas valve knob to OFF and turn 

the  electrical  supply  switch  to  OFF;  then  remove  the-

· 

pressure tap at the gas valve and re-install the plug, using 

a  compound 

{

on the  threads)  resistant  to  the  action of 

LP 

gases. 

11 

Summary of Contents for PBNU-LD06N040

Page 1: ...th low NOx mlss 9ns o 35 nanograms joule 100 shut off main gas valve for extra safety Propane modet convertible to natural gas PSG multlpte speed direct dove mJtor with large quiet blower 24V 40 VA co...

Page 2: ...g Extinguish any open flames Immediately call your gas supplier from a neighbor s phone Folio the gas sup plier s instructions If you cannot reach your gas supplier call the fire department 035 10976...

Page 3: ...are not handled property CAUTION The cooling coil must be installed in the supply air Condensate Piping 9 Electrical Data 9 Electrical Connections 9 10 Safety Controls 10 Start Up Adjustments 10 11 I...

Page 4: ...water codes and other applicable codes CAUTION Do notinstall the furnace in an unconditioned space or garage that could experience ambient temperatures of 3Z F 0 8 or lower CAUTION This unit must be...

Page 5: ...ia K O CAS INLcr f tr l 114 x VENT OOTLET 3 dia K O 2 8 1 2 LEFT SIDE 2 7 16 _ c D 11 2 15 2 15 2 21 2 21 3 21 3 21 3 25 3 Blower Max Outlet Temp HP Size OF 175 1 5 9 4 175 113 1 6 175 1 2 11 8 175 1...

Page 6: ...ere vent gas coutd enter the building 1 foot Above grade and anticipated snow depth 1 foot Above rade when adjacent to a publtc walkway _ 7 feet From electric gas meters regulators and rehef equipll e...

Page 7: ...his procedure To remove a filter from the side location push the closed end of the filter retainer down until it clears the flange on the side panel which acts as a catch for the retainer When the ret...

Page 8: ...s including pilots Do not breatht vapors and avoid contact with skin and eyes 6 All joints must be made to provide a permanent air tight water tight seal The only exception to this means o joining is...

Page 9: ...ame color as the building to make them less noticeable RGURE 6 ROOFTOP TERMINATION If optional side walt venting is to be used installation of the terminal kit should be as shown in Figures 7 and 8 Th...

Page 10: ...ocedure for condensate piping is as follows 1 Determine whether the condensate drain line will be in stalled through the right or left side of he furnace Unitary Products Group 650 65 N2 2 Carefully r...

Page 11: ...rminal board on the low voltage transformer Typical control wiring is shown in Figure 1OA Set the heat anticipator in t he room thermostat to 1 16 amps Setting it lower will cause short cycles Setting...

Page 12: ...surface igniter to begin glowing c If glow is seen turn the thermostat down below room temperature Hot surface igniter should stop glowing 3 Tum the gas supply ON at external valve and main gas valve...

Page 13: ...lly has a 1 2 or 1 cubic foot test dial 3 Using the number of seconds for each revolution and the size of the test dial increment find the cubic feet of gas t _ L L I TABLE 3 GAS RATE CUBIC FEET PER H...

Page 14: ...lay 3R which energizes the venter When the proper amount of combustion air is being provided a pressure switch activates the SOE47 ignition control A sec ond and third pressure switch 2LP or 3LP and 4...

Page 15: ...xchanger 1 Turn off the main manual gas valve extern to the furnace 2 Turn off the electrical power to the furnace 4 Disconnect the gas supply piping and control wiring from the gas valve 5 Remove the...

Page 16: ...rain trap has been emptied during this cleaning procedure refill it by following the instructions foundin the start Up andAdjustment section on this instruction 650 65 N2 13 Operate the unit for a min...

Page 17: ...2Jl Jl llP 2L lrS 1IIP TS IS IP 0 rn 6 o R lllm E Lilt lUI CN ICITCJl flUY II 1 M R I TOO flUY CDC flUr rrCJl ttJTm W TT 1l lflTOl IX Oll SWITOi SYI I Ol lltOit T ROO 24 110 i vtRIte tt1 LOO 115 X T I...

Page 18: ...ffi l l KJTrn B FETf NITG UXXli l l tlTG l tITGl F fl JRR fl ilTD 1 ocx KETI PllXl 24 YQT V RII ll ro J E TI PlLO liS VQT r AII ll ro xE1 Tarf 2 VIIS YQT lim ro xFTI PlLO 1 EtilTCJI Iill Tl COifFa a m...

Page 19: ...ansformer thermostat controller and wiring Place jumper on Place jumper pressure switch 1 LP on relay 3R Replace I between C NC between 1 3 venter Venter Okay Venter Okay YES YES r Check hoses connect...

Reviews: