HE 5750 Operating Instructions
#371627 | Version 1.1
71
12.2 Data direction PLC -> HE 5750
Position
Bit
Function
Data type
Bytes
Parallel Interface (IN)Bit
0
Commands
Digital
1
0
Filter start
unsigned char
X
1
Filter stop
X
2
Quick Hold (emergency stop)
X
3
Alarm reset
X
4
Requirement Offline cleaning
X
5
Requirement post-cleaning
X
6
Requirement forced cleaning
X
7
Parallel valve triggering locked
1
Commands
Digital
1
0
Local operation locked
unsigned char
X
1
Remote control
X
2
Cancel local ‘Chamber close’
3
Delta-p offset activated
4
Time synchronised
5
Dust monitoring locked
6
Deactivating modem interface
7
Toggle Bit
2
Close chamber
Digital
1
0
Chamber 1
unsigned char
X
to
X
7
Chamber 8
X
3
Close chamber
Digital
1
0
Chamber 9 to
unsigned char
7
Chamber 16
4
Close chamber
Digital
1
0
Chamber 17 to
unsigned char
7
Chamber 24
5
Chamber cleaning
Digital
1
0
Chamber 1 to
unsigned char
7
Chamber 8
6
Chamber cleaning
Digital
1
0
Chamber 9 to
unsigned char
7
Chamber 16
7
Chamber cleaning
Digital
1
0
Chamber 17
to
unsigned char
7
Chamber 24
8
Delta-
p offset ‘lower threshold‘
signed int
2
10
Delta-
p offset ‘upper threshold‘
signed int
2
12
Extra Pause 1st cycletime
unsigned int
2
14
Extra Pause 2nd cycletime
unsigned int
2
16
reserved
4
Test functions
20
Test command
Digital
1
1 = valve test
2 = Chamber cleaning
3 = damper controller
4 = isolation valves
unsigned char
21
Chamber number
unsigned char
1
22
Valve number
unsigned char
1
23
Damper selection
Digital
1
0
Raw gas damper 1
unsigned char
1
Raw gas damper 2
2
Pure gas damper 1