HE 5750 Operating Instructions
#371627 | Version 1.1
73
12.3 Data direction HE 5750 -> PLC
Position
Bit
Function
Data type
Bytes
Parallel Interface (Out)
0
Status information part 1
Digital
1
0
Cleaning activated
unsigned char
X
X
1
Filter Hold (emergency stop)
X
X
2
Offline cleaning activated
X
3
Cleaning running
X
X
4
Post-cleaning running
5
Forced cleaning running
6
Chamber cleaning running
7
Local operation unlocked
1
Status information part 2
Digital
1
0
Test function activated
unsigned char
1
Delta-p offset activated
2
Time synchronised
3
Background cleaning in process
4
Dust monitoring locked
5
Modem interface deactivated
6
Parallel valve triggering locked
7
Toggle Bit
2
Current chamber
unsigned char
1
3
Current valve
unsigned char
1
4
Chamber closed
Digital
1
0
Chamber 1 to
unsigned char
7
Chamber 8
5
Chamber closed
Digital
1
0
Chamber 9 to
unsigned char
7
Chamber 16
6
Chamber closed
Digital
1
0
Chamber 17
unsigned char
to
7
Chamber 24
7
Chamber cleaning active
Digital
1
0
Chamber 1 to
unsigned char
7
Chamber 8
8
Chamber cleaning active
Digital
1
0
Chamber 9 to
unsigned char
7
Chamber 16
9
Chamber cleaning active
Digital
1
0
Chamber 17 to
unsigned char
7
Chamber 24
10
Alarms part 1
Digital
1
0
Common alarm
unsigned char
X
1
Differential pressure alarm
X
2
Error cleaning system pressure
X
3
Error pressure in chamber pres.
manifold
X
4
Error Isolation valve
X
5
Valve error
X
6
Hopper level high
X
7
Exceed threshold dust
X
11
Alarms part 2
Digital
1
0
Error raw gas damper
unsigned char
X
1
Error pure gas damper
X
2
Error CAN bus
3
Flow rate sensor error
X
4
Wrong command from PLC