background image

Data  subject  to  change  without  notice.  For  more  information  visit  our  website:  www.helvar.com

9

Notes:

•  “Manual  ON, Automatic  OFF”  feature  =  PIR  will  not  switch  the  lights  on  when  movement  is

detected, but will switch them off if no movement is detected.

• Regardless of other light level commands (e.g. changes in the constant light level), an enabled

PIR will switch the lights to the PIR OFF scene  if no movement is detected within its programmed

delay time.

Presence detector (PIR)

• Simultaneously press & hold “

3

” & “

4

” for 10 seconds.

• The operation is confirmed by flashing the lamps.

Note:

This also resets all scenes.

10 seconds

1

3

4

2

0/1

Disable “Manual ON, Automatic OFF” feature

(only possible through initial configuration / minisensor reset)

1

3

4

2

0/1

10 seconds

10 seconds

1

3

4

2

0/1

• Simultaneously press & hold “

0/1

” & “

2

” for 10 seconds.

• Simultaneously press & hold “

0/1

” & “

3

” for 10 seconds.

Note:

This must be done before setting the PIR delay time. If

you require a different delay time please see PIR delay

time settings instructions

.

Enable “Manual ON, Automatic OFF” feature with 20seconds delay time

1

3

4

2

0/1

10 seconds

1

3

4

2

0/1

10 seconds

• Simultaneously press & hold “

0/1

” & “

2

” for 10 seconds.

• Simultaneously press & hold “

0/1

” & “

4

” for 10 seconds.

Note:

This must be done before setting the PIR delay time. If

you require a different delay time please see PIR delay

time settings instructions.

Enable “Manual ON, Automatic OFF” feature with 20min. delay time

1

3

4

2

0/1

10 seconds

• Simultaneously press & hold “

0/1

” & “

2

” for 10 seconds.

• The operation is confirmed by flashing the lamps.

Disable PIR.

10 seconds

1

3

4

2

0/1

• Simultaneously press & hold “

3

” & “

4

” for 10 seconds.

• The operation is confirmed by flashing the lamps.

Note:

This also resets all scenes.

Enable PIR 

(only possible through initial configuration / minisensor reset).

Summary of Contents for Minisensor

Page 1: ...Minisensor User guide Ref 2 0 1 ...

Page 2: ...n 4 Reception areas 4 Quick functionality guide 5 Out of box operation 6 Initial configuration Minisensor reset 6 Infrared IR control 7 Constant light channel A 8 Presence detector PIR 9 PIR delay time setting last level function 11 Recommendations 12 Fault finding 12 Technical spesifications 13 Appendixes Recommended programming sequence A Programming examples B ...

Page 3: ...lighting control The constant light sensor only adjusts the output from channel A where as presence detection infrared control affect both channels The Minisensor is only compatible with the Helvar EL si electronic DALI ballast range Sensor set up programming is achieved using the Helvar Digidim infrared remote control Dimensions Installation 3 3mm 25mm 32mm max 1 2mm 4mm Clip on assembly Surface ...

Page 4: ...r PIR Constant light sensor Infrared IR control 5 0m 7 0m 0 8m 3 0m 100o Connection Maximum connection Up to 4 ballasts per Minisensor Combinations are found from the following table Example connection Ch A 2pcs Ch B 1pcs 4 5m 3 0m Orientation PIR Lead color Yel Bl Gr Rd Polarity 1 0 No of ballasts Channel A B 0 4 1 2 3 4 3 2 ...

Page 5: ...Data subject to change without notice For more information visit our website www helvar com 5 Quick functionality guide Practical configuration example enclosed in appendix B example 2 ...

Page 6: ...ht level After an additional 20 seconds switch lights off IR receiver enabled Last level recall function disabled Basic lighting scenes stored 100 scene 1 75 scene 2 50 scene 3 25 scene 4 100 PIR ON light level scene 1 PIR LOW Light Level scene 0 PIR OFF light level scene 10 seconds Out of box operation Simultaneously press hold 3 4 for 10 seconds to install initial settings The operation is confi...

Page 7: ...n buttons 1 to 4 will replace any previously stored preset light levels Modify and store preset light levels Use the remote control or keys to adjust the lighting of channel A B to the desired level Press hold for 10 seconds the desired remote control scene button 1 2 3 or 4 where you would like the preset level to be stored The operation is confirmed by flashing the lamps Modify and store scenes ...

Page 8: ...fected by the PIR The stored constant light level is not affected by switching the lights off The stored constant light level is equal to the PIR ON level Enable constant light function only possible through initial configuration minisensor reset Simultaneously press hold 3 4 for 10 seconds The operation is confirmed by flashing the lamps Note This also resets all scenes Disable constant light fun...

Page 9: ...ess hold 0 1 2 for 10 seconds Simultaneously press hold 0 1 3 for 10 seconds Note This must be done before setting the PIR delay time If you require a different delay time please see PIR delay time settings instructions Enable Manual ON Automatic OFF feature with 20seconds delay time 1 3 4 2 0 1 10 seconds 1 3 4 2 0 1 10 seconds Simultaneously press hold 0 1 2 for 10 seconds Simultaneously press h...

Page 10: ... control section Simultaneously press hold 0 1 for 10 seconds The operation is confirmed by flashing the lamps Note This also sets the Constant light level Select the overall desired light level See Infrared IR control section Notes Regardless of other light level commands e g changes in the constant light level an enabled PIR will switch the lights to the PIR OFF scene if no movement is detected ...

Page 11: ...shing the lamps If you need to choose a shorter time than already in use you must start the sequence from the beginning Test setting This mode should only be used to test the functionality during installation In test mode the Constant light response time is 20 times quicker than in normal operation and should only be used for demonstration or test purposes To select short PIR delay times Press and...

Page 12: ...lvar EL si ballast The Minisensor cannot be directly connected to the DALI interface Fault finding Fault Possible causes Incorrect connection No power applied to the ballast No response to scene buttons on the remote control Preset levels are not installed carry out reset Scenes programmed to off Batteries flat Lights do not dim Flat weak batteries in IR No scenes or levels preset Constant light d...

Page 13: ... Helvar EL si electronic ballast Operation conditions Ambient temperature range 0 C to 50 C Storage temperature range 10 C to 70 C Relative humidity 90 maximum non condensing Conformity Standards Safety Only valid if sensor is mounted in the same fitting as the ballasts Safety EN61347 2 11 EN61347 1 EN60598 1 IP rating 44 Isolation 4kV Finish White thermoplastic Protection Single insulation Wire l...

Page 14: ...en select Yes or No for each step and follow the instructions on referred pages Step 0 start Initial configuration Alter levels Set scenes No No No No No No No Yes Disable PIR Step 4 Page 6 Step 1 Step 2 Step 3 Step 5 Step 7 Step 6 Page 7 Program PIR light levels Disable Constant light Program Constant light levels Enable Manual on automatic off Yes Page 9 Yes Page 10 Yes Page 8 Yes Page 8 Yes Pag...

Page 15: ...eature page 9 i Simultaneously press hold 0 1 2 for 10 seconds ii Simultaneously press hold 0 1 4 for 10 seconds 4 Change the PIR delay time to 30 minutes page 11 i Simultaneously press hold 0 1 3 for 10 seconds ii Simultaneously press hold 0 1 4 for 10 seconds iii Simultaneously press hold 0 1 4 for 10 seconds Energy saving lighting with Presence detector and Constant light features Lights will g...

Page 16: ...Fax 39 02 55 30 10 32 United Kingdom Helvar Merca Limited Hawley Mill Hawley Road Dartford Kent DA2 7SY United Kingdom Tel 44 1322 282 258 Fax 44 1322 282 259 Germany Helvar Merca GmbH Carl Zeiss Strasse 12 D 63322 Rödermark Germany Tel 49 6074 92090 Fax 49 6074 920923 Sweden Helvarmerca AB Bultgatan 40B S 44240 KUNGÄLV Sweden Tel 46 303 246 950 Fax 46 303 588 75 F13 102 1D 13 01 05 Contact inform...