11
STEP 1VH – Press
and
simultaneously for three seconds and release, then press
and
simultaneously and release. Software version is displayed. Power supply is on left side of
display.
STEP 2VH – Days, total since start-up: This display shows the total days since startup. Press
the NEXT button to go to Step 3VH. Press REGEN to return to previous step.
STEP 3VH – Regenerations, total number since start-up: This display shows the total number
of regenerations that have occurred since startup. Press the NEXT button to go to Step 4VH.
Press REGEN to return to previous step.
STEP 4VH – Volume, total used since start-up: This display shows the total gallons treated
since startup. This display will equal zero if a water meter is not installed. Press NEXT button to
exit Valve History. Press REGEN to return to previous step.
STEP 5VH – Error Log history: up to 10 errors. Press
and
buttons to view each recorded
error. If no errors have occurred " – – – –" is displayed. With STALL ERRORS, right upper corner
of display indicates piston position at time of stall. Press NEXT to exit valve history.
STEP 1VH
➔
VALVE HISTORY
➔
STEP 2VH
970
TOTAL DAYS
STEP 3VH
235
➔
STEP 4VH
175
➔
GAL
x1K
RETURN TO NORMAL MODE
(Can not be reset)
TOTAL REGENS
TOTAL GALLONS
STEP 5VH
1- - -
➔
ERROR LOG
STEP 6D
12.7
➔
RETURN TO NORMAL MODE
GAL
MAX FLOW
DAY
6
STEP 6D – Flow rate, maximum of each of last seven days: The maximum flow rate in gallons
per minute that occurred in each of the last seven days will be displayed. Press
arrow to dis-
play maximum flow rate today = 0, yesterday = 1. This display will equal zero if a water meter is
not installed. Press the NEXT button to go to Step 7D. Press REGEN to return to the previous
step.
STEP 7D – MAV Drive History – Not displayed if MAV set to off.
• First - Average of 1st three drive times of MAV in that direction
• Last - Last drive time measured for that MAV in that direction
• Ave - Average drive time measured for MAV in that direction
• TTT - Drive time (1424 = 14.24 seconds)
• CCC - Total number of cycles for that MAV
• VVV - Relative drive voltage
MAV drives piston "in" is designated by (-) sign.
MAV drives piston "out" is designated by (+) sign.
Any time MAV is rebuilt or replaced, reset diagnostics to reflect new drive characteristics.
STEP 7D
CCC
➔
ALT-FIRST
CYC
TTT
VVV
XXXX