Boiler Location Considerations
•
Ambient room temperature always above 32°F (0°C) to
prevent freezing of liquid condensate.
•
Approved for installation in closets.
•
Protect gas ignition system components from water
(dripping, spraying, rain, etc.) during operation and
service (circulator replacement, condensate trap, control
replacement, etc.).
•
Wall mount, optional floor stand available.
•
Determine alternate User Interface mounting location
if desired. See page 81 - Optional User Interface
Relocation.
•
Access to outdoors to meet minimum and maximum
pipe lengths for combustion air and vent piping. See
section 6.
•
Disposal of condensate. See section 6.
•
Drainage of water (or water - antifreeze solution) during
boiler service or from safety relief valve discharge. See
section 5.
•
Access to system water piping, gas supply, and electrical
service. See sections 5, 7 and 8.
•
Clearances to combustible materials and service
clearances. See Table 2 and figure 4-1.
•
Multiple Boilers can be wall mounted, placed side by
side,
or
back to back.
TABLE 2: BOILER CLEARANCES
Dimension
Combustible
Materials
(1)
Service
(1)(2)
Model 050/075/100/
150/200
050/075/100/
150/200
Top (A)
0" (0 cm)
14" (36 cm)
Left Side (B)
0" (0 cm)
0" (0 cm)
Right Side (C)
0" (0 cm)
0" (0 cm)
Front (D)
0" (0 cm)
6" (16 cm)
Back (E)
0" (0 cm)
0" (0 cm)
Bottom (F)
0" (0 cm)
12" (32 cm)
Combustion Air/Vent
piping
0" (0 cm)
6" (16 cm)
Hot Water Piping
See local code
6" (16 cm)
(1)
Required distances measured from boiler jacket.
(2)
Service, proper operation clearance recommendation.
A
C
B
A
F L O O R
F L O O R
F
F
4 - LOCATING BOILER
FRONT OF BOILER
LEFT SIDE
OF BOILER
A
E
E
D
F
F
Summary of Contents for VX-050
Page 49: ...49 13 TROUBLE SHOOTING...
Page 51: ...51 13 TROUBLE SHOOTING...
Page 63: ...63 14 1 Connection Diagram 050 075 100 MBH 14 WIRING DIAGRAM...
Page 64: ...64 14 2 Schematic Diagram of Ladder Form 050 075 100 MBH 14 WIRING DIAGRAM...
Page 65: ...65 14 3 Connection Diagram 150 200 MBH 14 WIRING DIAGRAM...
Page 66: ...66 14 4 Schematic Diagram of Ladder Form 150 200 MBH 14 WIRING DIAGRAM...
Page 83: ...83 PRIMARY LOOP EQUIVALENT LENGTH CALCULATION PUMP SELECTION 50 75 100 MBH...
Page 84: ...84 PRIMARY LOOP EQUIVALENT LENGTH CALCULATION PUMP SELECTION 50 75 100 MBH...
Page 85: ...85 PRIMARY LOOP EQUIVALENT LENGTH CALCULATION PUMP SELECTION 150 200 MBH...
Page 86: ...86 PRIMARY LOOP EQUIVALENT LENGTH CALCULATION PUMP SELECTION 150 200 MBH...
Page 87: ...87 NOTES...
Page 88: ...DUNKIRK BOILERS 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com...