24
Side Wall
Terminations
3" (80mm) Minimum horizontal
separation between combustion air
intake and vent terminations.
8" (203mm) Minimum vertical
separation between combustion air
intake and vent terminations.
12" (305mm) Separation between
bottom of combustion air intake and
bottom of vent.
Multiple terminations as shown
in 6-1, 6-2, and 6-3 must be
a minimum of 12” (305mm)
horizontally between vent of one
termination and air intake of next
appliance.
Maximum allowable total outside
exposure vent length equals 10 ft.
(3.05m).
Maintain a pitch of 1/2" per ft.
(13mm/m) outside exposure back to
boiler to ensure proper condensate
drainage for horizontal runs.
Roof
Terminations
3" (76mm) Minimum horizontal
separation between combustion air
intake and vent of same appliance.
8" (203mm) Minimum vertical
separation between combustion
air intake and vent of different
appliances.
15" (381mm) Maximum horizontal
length of vent.
Minimum vent/intake between
different appliances 12" (305mm).
Maximum allowable total vertical
vent length with outside exposure is
10 ft.(3.05m).
Abandoned unused masonry
chimney may be used as chaseway
for combustion air and vent. Both
combustion air and vent pipe must
exit above top of chimney with
clearances as shown in figure 6-1.
12" (305mm)
Minimum
8" (203mm)
Minimum
15" (381mm)
Maximum
3" (76mm)
Minimum
Vent
Combustion
Air
12" (305mm) US,
18" (457mm) Canada
Minimum Above
Anticipated Snow Line
Vent
3" (76mm)
Minimum
Separation
12" (305mm)
Minimum From
Overhang
12" (305mm) Separation
Between Bottom Of
Combustion Air Intake And
Bottom Of Vent
See Snow & Ice
Page 26
Combustion Air
Vent
12" (305mm)
Minimum
Separation
See Snow & Ice
Page 26
FIGURE 6-1 Two Pipe Roof Vent
FIGURE 6-2 Two Pipe Side Wall Vent
FIGURE 6-3 Two Pipe Side Wall Vent (Multiple Appliances.
Combustion Air
Roof Line
6 - COMBUSTION AIR AND VENT PIPING
Summary of Contents for VX-050
Page 49: ...49 13 TROUBLE SHOOTING...
Page 51: ...51 13 TROUBLE SHOOTING...
Page 63: ...63 14 1 Connection Diagram 050 075 100 MBH 14 WIRING DIAGRAM...
Page 64: ...64 14 2 Schematic Diagram of Ladder Form 050 075 100 MBH 14 WIRING DIAGRAM...
Page 65: ...65 14 3 Connection Diagram 150 200 MBH 14 WIRING DIAGRAM...
Page 66: ...66 14 4 Schematic Diagram of Ladder Form 150 200 MBH 14 WIRING DIAGRAM...
Page 83: ...83 PRIMARY LOOP EQUIVALENT LENGTH CALCULATION PUMP SELECTION 50 75 100 MBH...
Page 84: ...84 PRIMARY LOOP EQUIVALENT LENGTH CALCULATION PUMP SELECTION 50 75 100 MBH...
Page 85: ...85 PRIMARY LOOP EQUIVALENT LENGTH CALCULATION PUMP SELECTION 150 200 MBH...
Page 86: ...86 PRIMARY LOOP EQUIVALENT LENGTH CALCULATION PUMP SELECTION 150 200 MBH...
Page 87: ...87 NOTES...
Page 88: ...DUNKIRK BOILERS 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com...