![HELIX VX-050 Installation, Operation & Maintenance Manual Download Page 62](http://html1.mh-extra.com/html/helix/vx-050/vx-050_installation-operation-and-maintenance-manual_2121164062.webp)
62
13 - TROUBLE SHOOTING
Temperature
°C
Temperature
°F
Resistance
0
32
36100
5
41
28590
10
50
22790
15
59
18290
20
68
14770
25
77
12000
30
86
9805
35
95
8055
40
104
6653
45
113
5524
50
122
4809
55
131
3863
60
140
3253
65
149
2752
70
158
2337
75
167
1994
80
176
1707
85
185
1467
90
194
1265
95
203
1095
100
212
952