6 Sensors
12
Digital Governor Basic System PANDAROS II
6
Sensors
6.1
Overview
Sensor
Speed
Coolant
Temperature
Oil Pressure
Boost Pressure
HZM - Designation
IA ..
TS 01-28-PT1000
DSO 01-6
DSO 01-10
DSL/G 0..-2
DSL/G 0..-5
DSL/G 0..-10
Connection
SV 6-IA-2K
2 pole
SV 6-IA-2K
2 pole
DIN 43650 A
2 line system
DIN 43650 A
2 line system
Measuring Procedure inductive, active
PT1000, passive
active
active
Measuring Range
50 ... 9.000 Hz
-50 ... +150°C
0 ... 6 bar
0 ... 10 bar
0 ... 2 bar
0 ... 5 bar
0 ... 10 bar
Supply Voltage
Range
passiv
10 ... 34 V DC
12 ... 36 V DC
Output Signal Range
0 ... 10 V AC
ca. 700 ... 1500 Ohm
4 ... 20 mA
4 ... 20 mA
Operating Tempera-
ture Range
-55 ... +120°C
-50 ... +150°C
-25 ... +125°C
-40 ... +100°C
In order to ensure maximum flexibility with regard to the sensors, the minimum/ maximum
current values and the measuring ranges of the pressure and temperature sensors have been
provided programmable.