E7
Operating Instructions and Owner’s Manual
Enerco Group, Inc. | Gas-Fired Infra-Red Space Heaters
2. ADJUSTING THE PILOT FLAME
Thepilotflameshouldenvelope3/8to½in.(10to13mm)
ofthetipoftheSpark/FlameSensor,depictedinFigure8.
Toadjustthepilotflame:
a.Removepilotadjustmentcoverscrew.RefertoFigure9.
b.Turninneradjustmentscrewclockwisetodecreaseor
counterclockwisetoincreasepilotflame.
c.Alwaysreplacecoverscrewafteradjustmentandtighten
firmlytoensureproperoperation.
3. MEANS OF PROVING ADEQUATE GROUNDING AREA
Theproperflame-rod-to-ground-arearatiocannot
alwaysbedeterminedbyvisualexaminationor
physicalmeasurement.Apositivemeansofchecking
theinstallationisthemeasurementoftheflamerod
currentunderactualfiringconditions.Itisdefinitely
recommendedthattheinstallermeasurethecurrent
flowbetweentheleadoftheflamerodunitandthe
terminalinthecontrolterminalboard(seeFigure7).
MeasurethecurrentwithaDCMicroammeterorequal.
Werecommendasteadyoutputof0.9microamperes
ormore.Asteadyflowofcurrentinthisamountunder
actualfiringconditionswillgenerallyindicateadequate
groundingofthepilotflame.
NOTE:
1. Readallcontroldatasheetsuppliedwiththisheater.
2. Checkflamerodforanycontacttoheaterparts.Flame
rodmustbefreeofanycontacttoheater.Contactwith
heaterwillshortcircuitflamerod.
3. Crackedporcelainonflamerodwillshortcircuitsensor.
Replaceflamerod.
Figure 7.
Using a microammeter to prove adequate grounding area
.
GND
V2
FENWALL
IGNITION MODULE
IND/
MV1
V1/PV1
TH/W
SPARK
120VAC
24VAC
24 VOLT
THERMOSTAT
OPTIONAL
LINE VOLTAGE
THERMOSTAT
OPTIONAL
TRANSFORMER
(SHIPPED LOOSE)
GAS VALVE
PV
PV/MV
MV
VALVE
GROUND
MAIN BURNER
PILOT BURNER
SPARK ELECTRODE/FLAME SENSOR
Figure 10.
Connection Diagram for
flame rod current
Figure 8. Proper Flame Adjustment
Figure 9. Top view of standard capacity gas control
392929_HSRR30-2017-WO-V9.indd 7