Heatrae Sadia Multipoint 10 and 15 litre Fitting Instructions Manual Download Page 8

8

WARNING

Failure to provide adequate pressure relief 

will invalidate any guarantee and lead to a 

dangerous installation.

 

`

Expansion can take place within the cold water 

supply provided that both :

• 

  Backflow in the main is not prevented by any 

stop valve with loose jumper, check valve, 

pressure reducing valve or similar, and

•    Hot water expansion does not enter a branch 

to a cold water outlet (see Figure 02 for 

expansion pipe lengths).

 

 Both the above conditions must be met. 

Additionally expansion within the cold water 

supply will not be possible if the static supply  

pressure exceeds 0.41 MPa (4.1bar).

 

`

If any of the conditions in above cannot be met, 

expansion must be accommodated using an 

Expansion Vessel. To ensure all expansion takes 

place in the vessel a Check Valve must also 

be  fitted  together  with  a  Pressure  (expansion) 

Relief Valve (see Figure 03). Use Accessory 

Pack U2 code no. 95 970 351.

 

`

If the static supply pressure exceeds 0.41 MPa 

(4.1 bar) a Pressure Reducing Valve must be 

fitted  to  the  cold  main  supply.  If  a  Pressure 

Reducing Valve is used, an Expansion Vessel 

must also be used (see Figure 04). Use 

Accessory Packs U1 and U2 Code No.’s 95 970 

352 and 95 970 351.

Discharge 

 

`

The discharge outlet from the Pressure 

(expansion) Relief Valve and the Temperature/

Pressure relief Valve must be connected to 

a discharge pipe. It is recommended that the 

tundish supplied be installed in the discharge 

pipe to give a visible indication that the valves 

are operating.

 

`

The discharge pipe must fall continuously from 

the valve outlets and be unobstructed, and in a 

frost-free environment.

 

`

The pipe from the valves to the tundish should 

be 15mm o/dia minimum. From the tundish to 

the point of discharge the pipe should be 22mm 

o/dia  minimum  and  have  a  resistance  to  flow 

equivalent to 9 metres of straight pipe. Long 

discharge pipe runs should have an increased 

internal diameter.

 

`

The water may drip from the discharge pipe of 

6.  Installation

6.1 General

After reading the previous sections in this booklet 

and choosing a good location for the product please 

install, paying attention to the following hydraulic, 

electrical and commissioning sections.

6.2 Water connections

WARNING

 

`

Under no circumstances should 

the  factory  fitted  temperature/

pressure relief valve be removed 

other than a competent person. To 

do so will invalidate any guarantee 

or claim.

 

`

No control or safety valve should 

be tampered with or used for any 

other purpose.

 

`

The discharge pipe should not 

be blocked or used for any other 

purpose.

 

`

The tundish should not be 

located adjacent to any electrical 

components.

Refer to the Installation schematic (figure 4-6, page 

6) to determine which valves and accessories are 

required. 

Plumb in the valves in the sequence shown in the 

relevant figures 4-6, page 6. 

 

`

The water connections are 15mm diameter 

copper  tubes  suitable  for  compression  fittings. 

Do not use solder joints as this will damage 

the heater and may prevent servicing under 

warranty.

 

`

The INLET is marked BLUE, the OUTLET is 

marked RED. The WRAS listed isolating valve 

(supplied)  must  be  fitted  on  the  cold  water 

supply to the product. Several hot outlets can 

be served. 

 

`

Plumbers Paste must not be used as it can 

impair the operation of the valves.

 

`

The  product  MUST  be  fitted  with  a  Pressure 

Relief  Valve.  The  factory  fitted  Temperature/

Pressure Relief Valve can fulfil this function.

Summary of Contents for Multipoint 10 and 15 litre

Page 1: ...Multipoint 10 and 15 litre Fitting Instructions...

Page 2: ...cise warranty details to customers Contents 1 Introduction 3 1 1 General 3 1 2 Symbols used 3 1 3 Abbreviations 3 1 4 Liabilities 3 2 Safety 4 2 1 General safety warnings 4 2 2 Recommendations 4 2 3 S...

Page 3: ...in product quality All the specifications stated in this document are therefore subject to change without notice Our liability as the manufacturer may not be invoked in the following cases Failure to...

Page 4: ...in any circumstance 2 Safety 2 1 General safety warnings DANGER This product is unvented and as such becomes pressurised when in operation The combination of pressurisation and hot water could lead t...

Page 5: ...maintained and disposed of at end of life See Section 3 11 Electrical rating 3kW 240V 2 75kW 230V 4 5kW 240V 4 1kW 230V Capacities 10 or 15 litres Weight full 10 litre 16 9kg 15 litre 23 8kg Rated pr...

Page 6: ...relief valve Pressure relief expansion valve Note If pressure reducing valve is used expansion down the mains is not possible Pressure relief expansion valve Pressure relief expansion valve Expansion...

Page 7: ...gineer in accordance with prevailing and national regulations as listed below Building Regulations The Building Standards Scotland The Building Regulations Northern Ireland I E E Electrical Regs UK Wa...

Page 8: ...environment The pipe from the valves to the tundish should be 15mm o dia minimum From the tundish to the point of discharge the pipe should be 22mm o dia minimum and have a resistance to flow equivale...

Page 9: ...t be earthed It is suitable for a c supply only Disconnect the electrical supply before removing the terminal cover Installation must be in accordance with the current I E E Wiring Regulations The pro...

Page 10: ...l After filling the installation with water in the previous section please follow the following steps to complete the installation of the product WARNING DO NOT switch on the product until it has been...

Page 11: ...d when using in conjunction with a Thermostatic Blending Valve position To lock the thermostat position the instructions given under Sections 4 2 3 or 4 2 4 should be followed We recommend that this p...

Page 12: ...y by unscrewing the five securing screws a tapped jacking point is provided Remove any loose scale from the container Carefully clean off any scale from the element and thermostat pocket DO NOT clean...

Page 13: ...relief valve intermittently A Expansion in mains not possible A Fit pack U2 see important installation points B Mains pressure exceeds 0 41 MPa 4 1 bar B Fit packs U1 and U2 C Pack U1 fitted without...

Page 14: ...oduct is manufactured from many recyclable materials At the end of its useful life it should be disposed of at a Local Authority Recycling Centre to realise the full environmental benefits Insulation...

Page 15: ...hin 60 days of installation the user completes and returns the certificate supplied along with proof of purchase to register the product The product is not covered against damage by frost and the imme...

Page 16: ...sponsibility and sustainability charters and reduce our printed material we encourage you to download product brochures from our website In designing these files we have taken into account the need to...