background image

Heatilator  •  HEIR36, HEIR42, HEIR50 Installation Manual  •  2285-980 Rev. G  •  12/14

26

A.  Pipe Clearances to Combustibles

WARNING! Risk of Fire! 

Maintain air space clearance 

to vent. 

DO NOT

 pack insulation or other combustibles:

• Between ceiling 

fi

 restops

•  Between wall shield 

fi

 restops

•  Around vent system
Failure to keep insulation or other material away from 
vent pipe may cause overheating and 

fi

 re.

Vent Clearances and Framing 

 

Figure 5.2  Wall Penetration

Figure 5.1  Horizontal Venting Clearances To Combustible
 Materials

B.  Wall Penetration Framing/Firestops

Combustible Wall Penetration

Whenever a combustible wall is penetrated, you must 
frame a hole for the wall shield 

fi

 restop(s). The wall shield 

fi

 restop maintains minimum clearances and prevents cold 

air in

fi

 ltration.

•  The opening must be framed on all four sides using the 

same size framing materials as those used in the wall 
construction.

•  DVP pipe - A wall shield 

fi

 restop is required on one side 

only on interior walls. If your local inspector requires a 
wall shield 

fi

 restop on both sides, then both wall shield 

fi

 restops must have a heat shield (refer to Section 

12.A.) attached to them.

•  See Section 7.E. for information for regarding the instal-

lation of a horizontal termination cap.

Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm). 

‡

DVP heat shield 

- designed to be used on a wall 4 in. to 7-1/4 in. (102 mm to 184 

mm)

 

thick

.

‡,IZDOOWKLFNQHVVLVOHVVWKDQLQWKHH[LVWLQJKHDWVKLHOGVPXVWEHILHOGWULPPHG,I

wall thickness is greater than 7-1/4 in. a DVP-HSM-B will be required.

‡,IZDOOWKLFNQHVVLVOHVVWKDQWKHH[LVWLQJKHDWVKLHOGVPXVWEHILHOGWULPPHG

,IZDOOWKLFNQHVVLVJUHDWHUWKDQLQD'93+60%ZLOOEHUHTXLUHG

(DVP Pipe Shown)

3 in. (76 mm)
top clearance *

LQPP

clearance
bottom & sides

Heat
Shield

Wall

Shield

Firestop

Heat
Shield

WALL

3 in. (76 mm)

top clearance

LQPP

clearance around
vertical sections

A*

B

10 in.

12 in.

DO NOT PACK WITH
INSULATION OR OTHER
MATERIAL

*  Shows center of vent framing hole with minimum vertical for top venting. The 

center of the hole is one (1) in. (25.4 mm) above the center of the horizontal 
vent pipe.

Non-Combustible Wall Penetration

If the hole being penetrated is surrounded by non-com-
bustible materials such as concrete, a hole with diameter 
one inch greater than the pipe is acceptable.
Whenever a non-combustible wall is penetrated, the wall 
shield 

fi

 restop is only required on one side and no heat 

shield is necessary.

MODEL

A*

B

HEIR36 

74-3/16 in.

73-3/16 in.

HEIR42  

79-3/16 in.

78-3/16 in.

HEIR50

83-3/16 in.

82-3/16 in.

Summary of Contents for HEIR36

Page 1: ...th other gases unless a certified kit is used Pour demander un exemplaire en fran ais de ce Manuel du propri taire visitez www heatnglo com translations HEIR36H HEIR36T HEIR42H HEIR42T HEIR50H HEIR50T...

Page 2: ...rances 16 B Chimney Diagram 17 C Approved Pipe 18 D Use of Elbows 18 E Measuring Standards 18 F Vent Diagrams 19 G PVK 80 and PVI SLP Information 25 5 Vent Clearances and Framing A Pipe Clearances to...

Page 3: ...sulation shield is installed if applicable ___________________ Veri ed Exterior wall Roof ashing is installed and sealed ___________________ Veri ed termination cap is installed and sealed ___________...

Page 4: ...sence of local codes with National Electric Code ANSI NFPA 70 latest edition or the Canadian Electric Code CSA C22 1 A 110 120 VAC circuit for this product must be pro tected with ground fault circuit...

Page 5: ...d gas fu eled heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or loca...

Page 6: ...e or substitute components Keep appliance dry B Tools and Supplies Needed Before beginning the installation be sure that the following tools and building supplies are available Tape measure Framing ma...

Page 7: ...nches Millimeters J 24 610 K 23 1 2 597 L 59 1 4 1505 M 16 406 N 29 5 8 752 O 3 7 8 98 P 2 3 4 70 Q 10 7 8 276 R 16 1 8 410 Location Inches Millimeters A 61 1549 B 35 7 8 911 C 39 7 8 1013 D 31 1 16 7...

Page 8: ...406 N 32 11 16 830 O 3 7 8 98 P 2 3 4 70 Q 10 7 8 276 R 16 1 8 410 Location Inches Millimeters A 67 1702 B 41 7 8 1064 C 45 7 8 1165 D 36 1 16 916 E 62 5 8 1591 F 40 3 16 1021 G 39 3 16 995 H 59 15 16...

Page 9: ...AM HEIR36 See Section 10 for facing and finishing detail Figure 3 3 Decorative Front Dimensions HEIR36 40 11 16 IN 1035 mm 35 7 16 IN 900 mm 31 5 8 IN 803 mm 36 3 4 IN 934 mm 3 5 8 IN 92 mm 1 5 16 IN...

Page 10: ...ions HEIR42 DECORATIVE FRONT DIMENSION DIAGRAM HEIR42 See Section 10 for facing and finishing detail 46 11 16 IN 1186 mm 40 9 16 IN 1030 mm 36 3 4 IN 934 mm 3 9 16 IN 91 mm 1 1 4 IN 32 mm FS 42A 1 1 4...

Page 11: ...ions HEIR50 DECORATIVE FRONT DIMENSION DIAGRAM HEIR50 See Section 10 for facing and finishing detail 54 11 16 IN 1390 mm 44 7 16 IN 1129 mm 40 5 8 IN 1032 mm 45 11 16 IN 1161 mm 3 9 16 IN 91 mm 1 1 4...

Page 12: ...lustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY Illustrations diagrams are not drawn to scale Actual installation may vary due to individual design preference Figure 3 6 App...

Page 13: ...LES IN HATCHED AREA 1 2 IN BUILDING MATERIAL MAY BE COMBUSTIBLE FACTORY SUPPLIED 1 2 IN NON COMBUSTIBLE BOARD PIPE IS FOR VISUAL REFERENCE ONLY 1 IN COMBUSTIBLES NOT ALLOWED 39 IN 2 X 4 FRAMING MATERI...

Page 14: ...Risk of Fire Maintain specified air space clearances to appliance and vent pipe Insulation and other materials must be secured to prevent accidental contact The chase must be properly blocked to prev...

Page 15: ...appliance must be raised by the equivalent height to ensure that the hearth extension does not interfere with the installation of the glass assembly required for fireplace operation See Figure 3 10 Fi...

Page 16: ...n or other materials Failure to keep insulation or other materials away from vent pipe may cause overheating and fire WARNING Figure 4 2 Staggered Termination Caps Gas Wood or Fuel Oil Termination Cap...

Page 17: ...ly dwellings and serves both dwellings V VENT TERMINAL AREA WHERE TERMINAL IS NOT PERMITTED N 6 inches non vinyl sidewalls 12 inches vinyl sidewalls O 18 inches clearance below an unventilated ventila...

Page 18: ...th of straight pipe is allowed between two 45 elbows See Figure 4 4 Figure 4 5 shows the vertical and horizontal offsets for DVP elbows Figure 4 4 HORIZONTAL VERTICAL RUN RISE E F F E C T I V E L E N...

Page 19: ...gree or 45 degree elbow Horizontal termination cap should have a 1 4 inch downward slant to allow any moisture in cap to be released H1 V1 1 Top Vent Horizontal Termination Figure 4 6 One Elbow Note F...

Page 20: ...P models require a minimum of 36 inches of vertical venting before attaching any elbow to the appliance for the venting configuration in Figure 7 4 DO NOT attach elbow directly to the appliance HEIR36...

Page 21: ...ft 610 mm H2 Max 2 X V2 4 ft 1 2 m 4 ft 1 2 m H2 Max 2 X V2 5 ft 1 5 m 9 ft 2 7 m H2 Max 2 X V2 6 ft 1 8 m 12 ft 3 7 m H2 Max 2 X V2 7 ft 2 1 m 14 ft 4 3 m H2 Max 2 X V2 10 ft 3 0 m 20 ft 6 1 m H2 Ma...

Page 22: ...Vent Vertical Termination No Elbow V1 50 ft Max 15 2 m V1 2 ft Min 610 mm NOTE Flue Restrictor ships in manual bag assembly Note Flue restrictor is permit ted ONLY on 30 ft minimum vertical runs with...

Page 23: ...H1 V2 2 ft 610 mm 1 ft 305 mm 3 ft 914 mm 3 ft 914 mm 4 ft 1 2 m 4 ft 1 2 m 5 ft 1 5 m 9 ft 2 7 m 6 ft 1 8 m 12 ft 3 7 m V1 V2 H1 50 ft 15 2 m Max No specific restrictions on this value EXCEPT V1 V2...

Page 24: ...0 NG LP V1 H1 H2 V2 Ht Max 2 ft 610 mm 7 in 178 mm 3 ft 914 mm 2 ft 610 mm 4 ft 1 2 m 4 ft 1 2 m 5 ft 1 5 m 8 ft 2 4 m 6 ft 1 8 m 12 ft 3 7 m 7 ft 2 1 m 14 ft 4 3 m 10 ft 3 0 m 20 ft 6 1 m H1 and H2 h...

Page 25: ...Table 4 1 below for approved Power Venting options for HEIR models PVK 80 PVI SLP HEIR36 APPROVED APPROVED HEIR42 APPROVED APPROVED HEIR50 APPROVED APPROVED PVK 80 Exhaust Control Lever PVI SLP Baffl...

Page 26: ...or information for regarding the instal lation of a horizontal termination cap Note Heat shields MUST overlap by a minimum of 1 1 2 in 38 mm DVP heat shield designed to be used on a wall 4 in to 7 1 4...

Page 27: ...om the pipe to prevent overheating Figure 5 3 Installing Ceiling Firestop Figure 5 4 Installing the Attic Shield INSTALL ATTIC INSULATION SHIELDS BEFORE OR AFTER INSTALLATION OF VENT SYSTEM CEILING FI...

Page 28: ...orts on the left and right sides of the appliance See Figure 5 6 Remove the knockouts from the appliance with a tin snips Center the duct collar around the exposed hole and attach it to the appliance...

Page 29: ...g location of the seal cap and heat shields Section 6 splatter guard and finishing templates Section 10 and the logs and Lava Rock Section 11 2 Remove seal cap from top of appliance by removing one sc...

Page 30: ...ecure the appliance to the framing members See Figure 6 3 and Figure 6 5 for location of nailing tabs in shipping position Bend out side nailing tabs 90 degrees See Figure 6 4 Place the appliance into...

Page 31: ...shipped fastened to the top surround Remove finishing templates prior to installing non combustible board Remove non combustible facing pieces from back of appliance See Figure 6 6 Install non combus...

Page 32: ...or 90 and 45 elbows that are changing the vent direction from horizontal to vertical one screw minimum should be put in the outer flue at the horizontal elbow joint to prevent the elbow from rotating...

Page 33: ...ted every 8 ft 2 44 m after the maximum allowed 25 ft 7 62 m of unsupported rise Vertical runs originating off the rear of the appliance or after any elbow must be supported every 8 ft 2 44 m Horizont...

Page 34: ...S MIN H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING NOTICE Failure to properly caulk the roof flashing and pipe seams may permit entry of water Caulk the gap between the roof flashing and...

Page 35: ...ection of the termination cap MUST be used when connecting vent 1 1 2 38 mm minimum overlap of flue telescoping section is required Failure to maintain overlap may cause overheating and fire Vent term...

Page 36: ...e same wall box 8 8 Electrical Information Junction Box Installation The electrical junction box can be accessed three ways during installation 1 Through the access plate Remove two screws to release...

Page 37: ...eless controls be used for their features and functionality with the IntelliFireTM Plus ignition sys tem Figure 8 2 Junction Box Detail Electrical Service and Repair WARNING Risk of Shock Label all wi...

Page 38: ...n box to 110 120 VAC for proper operation of the appliance WARNING Risk of Shock or Explosion DO NOT wire IPI controlled appliance junction box to a switched circuit Incorrect wiring will override IPI...

Page 39: ...open flame Fittings and connections could have loos ened during shipping and handling WARNING Risk of Fire DO NOT change valve settings This valve has been preset at the factory WARNING Risk of Fire o...

Page 40: ...shutter is pre set at the factory for minimum vertical maximum horizontal vent run for this appliance 2 ft vertical and 7 in horizontal Factory Pre Set Air Shutter Settings To adjust air shutter Loos...

Page 41: ...verhang into the glass opening Observe all clearances when applying combustible materials WARNING Risk of Fire DO NOT apply combustible materials beyond the minimum clearances Comply with all minimum...

Page 42: ...inch thick The required decorative front will overlap finish materials less than one inch thick Refer to section 10 D for more information Remove template by removing the the two top screws and two sc...

Page 43: ...43 Heatilator HEIR36 HEIR42 HEIR50 Installation Manual 2285 980 Rev G 12 14 Figure 10 5 Finishing Template Bends...

Page 44: ...ION 10 D FOR REQUIRED CLEARANCES 7 IN MIN FIREPLACE OPENING COMBUSTIBLE OR NON COMBUSTIBLE WALL 14 IN MIN COMBUSTIBLE COLUMN 4 IN MAX 1 2 IN BUILDING MATERIAL FACTORY SUPPLIED NON COMBUSTIBLE BOARD NO...

Page 45: ...Combustible Mantel Allowance HEIR50 1 51 3 6 12 9 54 57 60 63 FIREPLACE OPENING 1 2 IN NON COMBUSTIBLE MATERIAL HEIR36 HEIR42 MAX MIN Measurement from fireplace opening to bottom of appliance 35 3 16...

Page 46: ...USTIBLE MATERIAL C ARCH Figure 10 13 Inside Fit Decorative Fronts The decorative fronts approved for use with this appli ance have been designed to be installed by two methods Overlap Fit or Inside Fi...

Page 47: ...etainer rail NOTICE Protect and prevent the hearth from damage by covering it with a drop cloth CAUTION Risk of Injury DO NOT put fingers under glass frame Fingers may get pinched by glass frame durin...

Page 48: ...glass clip See Fig ure 11 6 GRASP FRAME BY LIP THAT GRASP FRAME BY LIP THAT PROJECTS FROM GLASS DO NOT PROJECTS FROM GLASS DO NOT INSERT FINGERS UNDER RAIL INSERT FINGERS UNDER RAIL RAIL RAIL LIP LIP...

Page 49: ...l DO NOT place embers directly over burner ports Replace ember material annually Improperly placed embers interfere with proper burner operation Ember material is shipped with this gas appliance To pl...

Page 50: ...e bottom of Log 2 See Figure 4 Mate slots on the bottom of Log 2 with the left and center grate tines See Figure 5 Slide log forward toward front of appliance until left front of log contacts back of...

Page 51: ...tom of Log 3 See Figure 6 Place log as shown in Figure 7 Log should be centered on the right side of the burner Notches on log should rest on grate tine and burner pan The back left part of Log 3 shou...

Page 52: ...LOG 5 FOR LOG 5 FOR LOG 6 FOR LOG 6 Figure 12 Log 5 Placement Figure 13 Log 6 Placement Figure 14 Log Set Installed 4 4 3 3 1 1 2 2 6 6 6 6 5 5 2 2 3 3 5 5 1 1 4 4 1 1 3 3 2 2 5 5 Log 6 2284 706 Loca...

Page 53: ...acement tabs shown in Figure 1 See Figure 3 Figure 3 Log 2 2285 702 Locate log placement slots on the bottom of Log 2 See Figure 4 Mate slots on the bottom of Log 2 with the left and left center grate...

Page 54: ...actory Slide bottom of Log 4 toward front of appliance until it contacts back side of Log 2 Rest top of Log 4 in notch on top left corner of Log 1 See Figure 2 and Figure 9 Log 3 2285 703 Place log in...

Page 55: ...barrier removed Contact your dealer or Hearth Home Technologies if the barrier is not present or help is needed to properly install one For more information refer to the instructions supplied with yo...

Page 56: ...5 mm 12 in 305 mm 14 in 356 mm 1 in 25 mm 8 in 203 mm 6 in 152 mm 10 in 254 mm 1 1 2 in 38 mm 5 in 127 mm 12 in 305 mm UP DVP HVS Vent Support DVP WS Wall Shield Firestop DVP FS Ceiling Firestop DVP45...

Page 57: ...mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness...

Page 58: ...Cap Shield DRC RADIUS 13 7 8 in 352 mm 9 1 2 in 241 mm 14 in 356 mm COOL ADDM Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DVP BEK2 DVP HPC Cap Brick Extension 13 7 8 i...

Page 59: ...WH10 20 ft PV Wire Harness PVI WH20 40 ft PV Wire Harness PVI WH40 60 ft PV Wire Harness PVI WH60 80 ft PV Wire Harness PVI WH80 100 ft PV Wire Harness PVI WH100 PVI SLP Power Vent Inline SLP LPC SLP...

Page 60: ...ilator com Please contact your Heatilator dealer with any questions or concerns For the location of your nearest Heatilator dealer please visit www heatilator com B Accessories Install approved access...

Reviews: