20
Installing the Fireplace
(continued)
MINIMUM VERTICAL RISE = 9FT
MAXIMUM HORIZONTAL RUN = 15FT
V:H = 2:1
Figure 7. Vent System Attachment
Step 4
Installing the Vent System
A. Vent System Approvals
Models SL-550TV and SL-750TV are approved to use 5-inch
(127mm) diameter B-type vent. Model SL-950TV is approved
to use 6-inch (152mm) diameter B-type vent. B-type vent
must be used when the vent system is within combustible
construction.
These models may also use single wall rigid or flexible gas
vent
IF
and
ONLY IF
the vent system is installed within non-
combustible construction such as a masonry chimney. The
same diameters noted above for B-type vent must be used
for single-wall vent. See Figure 7.
Installation du foyer
(suite)
Étape 4
Installation du système dévacuation
A. Homologation du système dévacuation
Les modèles SL-550TV et SL-750TV sont approuvés pour
raccordement à un conduit dévacuation de type B de 127 mm
de diamètre. Le modèle SL-950TV est approuvé pour
raccordement à un conduit dévacuation de type B de 152 mm
de diamètre. Un conduit dévacuation de type B doit être
utilisé lorsque le système dévacuation est placé dans une
structure combustible.
Ces modèles peuvent également être utilisés avec un conduit
dévacuation des gaz rigide ou flexible à simple paroi
SI
et
SEULEMENT SI
le système dévacuation est placé dans
une structure non-combustible, telle une cheminée en
maçonnerie. Les mêmes diamètres que ceux qui sont
indiqués ci-dessus pour les conduits dévacuation de type B
doivent être utilisés pour les conduits dévacuation à simple
paroi. Voir Figure 7.
Figure 7. Installation du système dévacuation
LONGUEUR VERTICALE
MINIMALE = 274 cm
LONGUEUR HORIZONTALE
MAXIMALE = 457 cm
V:H = 2:1