HEAT PUMP SETUP
Number of Stages
– This setting will allow you to select
the number of heat pump stages that are attached to
the control.
If Backup is being used, you can only have a
maximum of 3 stages.
(1 to 4) Default: 1
Stage ON Lagtime
– When the heat pump is set for
more than 1 stage, this setting will be set for the
minimum lagtime between heat pump stages. This is
a time delay between stages. Even if the differential
has been exceeded this time must elapse before that
stage can come on.
(1-240 Min)
Stage Off Lagtime
– This feature is used to set how you
would like to stage the heat pumps off When the heat
pump is set for more than 1 stage, this setting will be
set for the minimum OFF lagtime between heat pump
stages
Rotate Time
– Rotate Time The time of rotation
between heat pumps. This setting is in hours of run
time. This means that the heat pumps are going to
rotate when the first heat pump exceeds the second
by the rotate time.
(OFF/1H to 240H) Default: OFF
Rotate Cycles
– Set the number of cycles at which
you would like to rotate the heat pumps. One cycle is
described as the heat pump going on and then off.
(OFF/1 to 240) Default: OFF
Off Staging
– This feature is used to set how you
would like to stage the heat pumps off. If set to OFF
the heat pumps will stage off normally based off of
tank temperature and differential settings or STAGE
OFF Lagtime settings. If set to ON the heat pumps
will all stage off at the same time, based off of tank
temperature and differential settings.
(OFF/ON) Default: OFF