H B X E C O - 0 6 0 0 G e o t h e r m a l C o n t r o l
V e r s i o n 1 . 0 . 0
Page 8
HOT TANK SETUP WITH OUTDOOR RESET
WWSD
- This setting is used to set the temperature in
which the ECO-0600 will go into WWSD. If the system
rises above this temperature, the system will be shut
off. In WWSD the heat pumps and backup boiler will
shut off.
(OFF/34°F to 180°F) Default: 65°F
Outdoor Reset (Design)
– This is used in the outdoor
reset design calculation. This option should be set to
reflect your specific city or region. This option needs to
be set OFF if you are not using outdoor reset.
*With this option enabled, the Tank Temperature
setting will be replaced by Min Tank and Max Tank
Temperature settings.
(OFF/-40°F to 127°F) Default: OFF
Differential
– Set this temperature to be the desired
hot tank differential.
*A differential of 4°F will allow for 2 degrees above
and/or 2 degrees below the desired temperature
before a demand is present.
(2°F to 100°F) Default: 6°F
Tank Target Temperature
- When a heat demand is
present and the control is not in WWSD, the control will
target this temperature for heating.
(35°F to 200°F) Default: 115°F
If there is no thermistor attached to pins 14 and 15, the
control assumes single tank operation.
TANK SETUP