COLD TANK SETUP WITH OUTDOOR RESET
CWSD
- This setting is used to set the temperature in
which the ECO-0550 will go into CWSD. If the system
goes below this temperature, the system will be shut
off. In CWSD the heat pumps will shut off.
(OFF/32°F to 119°F) Default: 75°F
Outdoor Reset (Design)
– This is used in the outdoor
reset design calculation. This option should be set to
reflect your specific city or region. This option needs to
setup as OFF if you are not using outdoor reset.
With this option enabled, the Tank Temperature
setting will be replaced by Min Tank and Max Tank
Temperature settings.
(OFF/0°F to 119°F) Default: OFF
Differential
– Set this temperature to be the desired
cold tank differential. A differential of 4°F will allow for
2 degrees above and/or 2 degrees below the desired
temperature before a demand is present.
(2°F to 100°F) Default: 8°F
Tank Target Temperature
- When a cooling demand is
present and the control is not in CWSD, the control will
target this temperature for cooling.
(30°F to 200°F) Default: 45°F
*If there is no thermistor attached to pins 14 and 15,
the control assumes single tank operation.