PME-MP70DP
72
A0658-7.3 en
HBM
After the “ERROR" status message, the display shows the status of the
PROFIBUS DP connection.
One
of the following status messages is shown in
each case:
BD_SEAR (baud rate search)
WT_PARM (waiting for parameter)
WT_CONF (waiting for configuration)
DATA_EX (cyclic data traffic)
ERROR (bus error)
The following applies for modules MP70DP and MP70DP‐S7:
The LEDs indicate the operating states (ready for measurement, overflow,
etc.,) of the module. However, instead of the CAN status (as with MP01,
MP30, MP55 and MP60), it is the PROFIBUS status that is displayed.
Operating status:
LED color
Status
Meaning
PROFIBUS status
Green
Steady light
DATA_EX status
Yellow
Steady light
BD_SEAR, WT_PARM, WT_CONF states
Red
Steady light
ERROR status
The realization of the other operating states corresponds to that of
measurement modules MP01, MP30, MP55 and MP60.
Operating status:
LED color
Status
Meaning
Measuring mode
Bus mode
Green
Steady
light
Ready for measurement
CAN Bus Operational (PDO
transfer possible)
Green
Flashes
Data being transmitted
over the interface
-
Yellow
Steady
light
Ready for measurement
CAN Bus PreOperational
(PDO transfer not possible)