69
PME-MP70DP
A0658-7.3 en
HBM
The configuration telegram therefore has the following format:
CFG
byte
Meaning
Permitted values for CFG (hex)
1
Header
0xC3..0xC9 (inputs and outputs, 3 - 9 bytes
manuf.‐specific data)
2
Length of outputs
0x40...0x48 (outputs of 1 to 9 words) or
0xC0...0xC8 (outputs of 1 to 9 words with consistency)
3
Length of inputs
0xC0 ... 0xCC or
0x40..0x7C (inputs of 1 to 13 words with/without consist
ency)
4
User‐specific data
Module type
input data
Data content selection
5
Module type
output data
6
7..12
CFG for module 1
as 1 - 5, but for module 1
13..18
CFG for module 2
as 1 - 5, but for module 2
19..24
CFG for module 3
as 1 - 5, but for module 3
25..30
CFG for module 4
as 1 - 5, but for module 4
31..36
CFG for module 5
as 1 - 5, but for module 5
37..42
CFG for module 6
as 1 - 5, but for module 6
43..48
CFG for module 7
as 1 - 5, but for module 7
49..54
CFG for module 8
as 1 - 5, but for module 8
Tab. 8.2:
Content of the configuration telegram
When using 32‐bit formats, it is essential to set data consistency.