USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
Page 16 of 76
HCP3000 SERIES Variable Speed Pump
ISHCP3000VSPC Rev -B
Connection wire must be rated for a minimum of 300V. See section 0.11 for more details. Do
not
connect to the lower
“COMBUS” or wall mount “DISPLAY” data terminals.
The HCP3000 SERIES Variable Speed Pump can also be controlled from third party pool controls using relay contacts
to select the speeds set in the Timer Menu (see section 6.7). In addition to this section you may also consult the
third party pool control installation manual for electrical connection details. Once installed, Remote Control Mode
must be set to Relay Control in the pump Configuration Menu (see section 0). Preset Speeds 1-4 and Quick Clean are
disabled when the pump is remotely controlled. When Inputs 1-3 are activated via the pool control relays, timer
speeds 1-8 are selected according to the following table:
Timer
Speed
INP1
Status
INP2
Status
INP3
Status
1 OFF
OFF
OFF
2 ON
OFF
OFF
3 OFF
ON
OFF
4 ON
ON
OFF
5 OFF
OFF
ON
6 ON
OFF
ON
7 OFF
ON
ON
8 ON
ON
ON
The number of speeds available depends on the number of auxiliary relays used as noted below:
1.
Filter pump relay plus 1 auxiliary relays allows control of 2 speeds
2.
Filter pump relay plus 2 auxiliary relays allows control of 4 speeds
3.
Filter pump relay plus 3 auxiliary relays allows control of 8 speeds
5.5 Remote Stop Switch Wiring (Optional)
Figure 5.5-1
Connection wire must be rated for a minimum of 300V. Switch must be latching type; pump is stopped when circuit
is closed.