5.5.10 Manual Reset Error Codes
– A##
Code
ENVI
™ Control Display
Lockout
Description
A00
NED
Unassigned
No Error Description, Call For Service
A01
IGNITION FAILURE
Ignition Failure
During an attempt to light, no flame was detected
A02
FLAME FAILURE
Flame Failure
During run, the flame was lost
A03
HIGH LIMIT
High Limit
The temperature in the boiler exceeded the setting on
the High Limit Control
A05
INT ERR GAS VLV RLY
Internal Error Gas Valve
Relay
Call for service.
A06
INT ERR SAFETY RLY
Internal Error Safety Relay
Call for service.
A07
LOW FLOW / ILK
Low Water Flow or Open
Interlock Jumper
Water Flow is Inadequate or
Interlock Jumper is Open
A09
INTERAL ERROR
9 or 27 or 28 or 29 or 30
Internal Error
9 or 27 or 28 or 29 or 30
Call for service.
A10
INT ERR E2PROM ERR
Internal Error E2PROM Err
Call for service.
A12
INT ERR E2PROM SIG
Internal Error E2PROM Sig
Call for service.
A13
INTERAL ERROR 13
Internal Error 13
Call for service.
A14
INTERAL ERROR 14
Internal Error 14
Call for service.
A15
INTERAL ERROR 16
Internal Error 16
Call for service.
A16
INTERAL ERROR 22
Internal Error 22
Call for service.
A18
INTERAL ERROR 19
Internal Error 19
Call for service.
A19
LATE FLAME
Late Flame
Flame still present after boiler gas valve closed during
post purge
A20
EARLY FLAME
Early Flame
Flame detected before boiler gas valve opened during
pre purge
A30
HIGH GAS PRESSURE
High Gas Pressure Error
The gas pressure is too high and has tripped the HGPS
or both gas valves have opened at the same time
A31
LOW GAS PRESSURE
Low Gas Pressure Error
The gas pressure is too low and has tripped the LGPS
A32
INTERAL ERROR 23
Internal Error 23
Call for service.
A33
FAN WRONG SPEED
Wrong Fan Speed Error
Fan deviation more than 300 rpm for > 1 sec (ignored
when fan > 4200 rpm)
A34
AIR SWITCH NOT OPEN
Air Switch Not Open
Air switch does not open when fan is off
A35
AIR SWITCH NOT CLOSE
Air Switch Not Closed
Air switch does not close when fan is running
A37
UV SENSOR DEFECT
UV Sensor Defective
Self Check function of UV detector has indicated a failure
A38
MAX DT EXCEEDED
Max Delta Temp Exceeded
Maximum temperature differential across the boiler has
been exceeded
A39
RAPID RISE INLET TMP
Rapid Rise Inlet Error
Inlet temperature is rising too rapidly
A40
RAPID RISE OUT TEMP
Rapid Rise Outlet Error
Outlet temperature is rising too rapidly
A41
RAPID RISE HX TEMP
Rapid Rise HX Temp
Temperature across heat exchanger is rising faster than
allowed
A43
LOW WATER LEVEL
Low Water Cutoff
Water is too low for boiler to operate
A45
INTERNAL ERROR 31
Internal Error 31
Call for service.
Note: When an Internal Error occurs, as identified above, the failu
re is internal to the ENVI™ boiler control and
replacement of the ENVI™ control is required. A qualified service technician must replace the ENVI™ control.