ACS-160 Series & STL-160 Series T1 Mux Installation & Operation
6-Testing & Troubleshooting
Version 2.11, August 2011
6-10
Harris Corporation
Intraplex Products
•
Create an external loopback by connecting a Bantam-Bantam patch cord from the T1 OUT
EQUIP jack to the T1 IN EQUIP jack.
•
Create an internal equipment loopback by using the GROUP and SET/NEXT switches to
activate the EqLB function (Section 6.3.1).
6.
Unseat all the channel modules in the multiplexer by pulling on their eject tabs but do not remove
them completely from the shelf. With no channel modules active, the T1 transmitter produces an
all-ones signal, which is looped back to the T1 receiver.
7.
Verify that the indicator lights respond (Table 6-6).
8.
Press all the channel modules firmly back into their sockets.
9.
Perform one or more channel tests using available VF, data, and other type test sets. These tests
might include level tests on voice channels, bit error tests on data channels, and so on (Figure 6-
9).
Note:
At this stage, you can perform channel tests only on 4-wire voice channels or full-duplex
data channels.
10.
When channel tests are complete, take down the loopback either by removing the patch cord or by
deactivating the equipment loopback.
11.
In a field test only – If the network configuration requires this multiplexer to use a timing source
other than internal, perform these steps to reset the timing source:
a.
Press down repeatedly on the GROUP switch until the display shows TIME.
b.
Press down repeatedly on the SET/NEXT switch until the display shows the desired timing
source (LOOP or EXT).
c.
Press up twice on the SET/NEXT switch to reset transmit timing to the source currently
displayed.
12.
Reconnect the T1 input/output connector (RJ-48C) to the MA-215 module adapter at the rear of
the CM-5RB module (or DB-15 on the MA-216 adapter).
Table 6-6. Indicator Lights in Terminal Multiplexer Loopback Test
CM-5RB Module
Indicator
Patch Cord
Loopback
EqLB
Loopback
TX OUT
ON
ON
RX IN
BLINKS
OFF*
ERR
OFF
OFF
YEL
OFF
OFF
BPV
OFF
OFF
AIS
OFF
OFF
FRM
OFF
OFF
INT
ON
ON
LPBK
OFF
ON**
CPU
OFF
OFF
NORMAL
ON
OFF
ALERT
OFF**
ON**
ALARM
OFF
OFF
* The RX IN light blinks to indicate detection of an all-ones signal. With an internal (EqLB) loopback
active, no signal reaches the T1 receiver.
Summary of Contents for ACS-163
Page 4: ...This page is left blank intentionally...
Page 52: ...No header 2 30 Harris Corporation Intraplex Products This page is left blank intentionally...
Page 144: ...No header 5 46 Harris Corporation Intraplex Products This page is left blank intentionally...
Page 166: ...No header 6 22 Harris Corporation Intraplex Products This page is left blank intentionally...
Page 172: ...No header 7 6 Harris Corporation Intraplex Products This page is left blank intentionally...